Function Parameter Reference Guide
12/00
UDC2300 Controller Product Manual
141
12.2.55 LOCK
(LOCKOUT)
This prompt is part of the Tuning Set up group.
LOCKOUT applies to one of the functional groups: Configuration, Calibration, Tuning,
Accutune.
DO NOT CONFIGURE UNTIL ALL CONFIGURATION IS COMPLETE.
.Selections
Definitions
NONE
No lockout; all groups are read/write
CAL
All groups are available for read/write except for the Calibration and
Keyboard Lockout groups.
CONF
Timer, Tuning, SP Ramp, and Accutune groups are read/write. All other
groups are read only. Calibration and Keyboard Lockout groups are not
available.
VIEW
Tuning and Setpoint Ramp parameters are read/write. No other parameters
can be viewed.
ALL
Tuning and Setpoint Ramp parameters are available for read only. No other
parameters can be viewed.
12.2.56 LOOPBACK
(LOCAL LOOPBACK TEST)
This prompt is part of the Communications Set up group.
Selections
Definitions
DIS
Disables the Loopback test
ENAB
Allows loopback test. The UDC goes into Loopback mode in which it sends
and receives its own message. The UDC displays PASS or FAIL status in
the upper display and LOOPBACK in the lower display while the test is
running. The UDC will go into manual mode. The test will run until the
operator disables it here, or until power is turned off and on.
ATTENTION
The UDC does not have to be connected to the RS-485 link
to perform this test. If it is connected, only one UDC2300 should run the
loopback test at a time. The computer should not be transmitting on the link
while the loopback test is active.
12.2.57
LSP’S
(LOCAL SETPOINT SOURCE)
This prompt is part of the Control Set up group.
This selection determines what your local setpoint source will be.
Selections
Definitions
ONE
LOCAL SETPOINT 1—The setpoint entered from the keyboard.
TWO
TWO LOCAL SETPOINTS—This selection lets you switch between two
local setpoints using the
FUNCTION
key.
Содержание UDC 2300
Страница 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Страница 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Страница 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Страница 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Страница 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Страница 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Страница 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Страница 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Страница 177: ......
Страница 178: ......
Страница 180: ......
Страница 181: ......
Страница 182: ......
Страница 183: ......
Страница 184: ......