Function Parameter Reference Guide
120
UDC2300 Controller Product Manual
12/00
12.2.4 A
TUNE
(AUTOTUNE KEY LOCKOUT)
This prompt is part of the Tuning Set up group.
This selection allows you to disable the
AUTOTUNE
key.
“LOCK” must be set to “None”.
Selections
Definitions
DIS
Disable the
AUTOTUNE
key
ENAB
Enables the
AUTOTUNE
key
12.2.5 ACTION
(CONTROL OUTPUT DIRECTION)
This prompt is part of the Control Set up group.
This selection allows you to select the direction you want the controller output to go when
the process variable increases.
Selections
Definitions
DIR
DIRECT ACTING CONTROL—The controller's output increases as the
process variable increases.
REV
REVERSE ACTING CONTROL—The controller's output decreases as
the process variable increases.
12.2.6 ALARM1
(LATCHING ALARM FOR OUTPUT)
This prompt is part of the Alarms Set up group.
Each alarm output can be configured to be Latching or Non-latching.
ATTENTION
When configured for latching, the alarm will stay on, after the alarm condition ends, until the
RUN/HOLD key is pressed.
Selections
Definitions
NO L
Non-Latching
LACH
Latching
Содержание UDC 2300
Страница 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Страница 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Страница 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Страница 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Страница 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Страница 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Страница 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Страница 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Страница 177: ......
Страница 178: ......
Страница 180: ......
Страница 181: ......
Страница 182: ......
Страница 183: ......
Страница 184: ......