Input Calibration
84
UDC2300 Controller Product Manual
12/00
Calibration Steps
Use the following steps when calibrating an input.
Step
Action
1
Find the minimum and maximum range values for your PV input range from Table 8-1.
2
Disconnect the field wiring and find out what equipment you will need to calibrate.
3
Wire the calibrating device to your controller according to the set up wiring instructions
for your particular input (Subsection 8.4 or 8.6).
4
Follow the calibration procedure given for Input #1 or Input #2 (Subsection 8.5 or 8.7).
8.2 Minimum and Maximum Range Values
Select the Range Values
You should calibrate the controller for the minimum (0 %) and maximum (100 %) range
values of your particular controller. If you have a two input controller, calibrate each
input separately.
Select the Voltage or Resistance equivalent for 0 % and 100 % range values from Table
8-1. Use these values when calibrating your controller.
Table 8-1 Voltage and Resistance Equivalents for Input 1 Range Values
PV Input Range
Range Values
Sensor Type
°F
°C
0 %
100 %
Thermocouples
B
0 to 3300
–18 to 1816
–0.100 mV
13.769 mV
E
-454 to 1832
–270 to1000
–9.835 mV
76.373 mV
E (low)
-200 to 1100
–129 to593
–6.472 mV
44.455 mV
J
0 to 1600
–18 to871
–0.886 mV
50.060 mV
J (low)
20 to 770
–7 to410
–0.334 mV
22.400 mV
K
0 to 2400
–18 to1816
–0.692 mV
52.952 mV
K (low)
–20 to 1000
–29 to538
–1.114 mV
22.255 mV
NiNiMoly (NNM68)
32 to 2500
0 to1371
0.000 mV
71.330 mV
NiNiMoly (low)
32 to 1260
0 to682
0.000 mV
31.820 mV
NiMo-NiCo (NM90)
32 to 2500
0 to1371
0.000 mV
71.773 mV
NiMo-NiCo (low)
32 to 1260
0 to682
0.000 mV
31.825 mV
Nicrosil Nisil (Nic)
0 to 2372
–18 to1300
–0.461 mV
47.513 mV
R
0 to 3100
–18 to1704
–0.090 mV
20.281 mV
S
0 to 3100
–18 to1704
–0.092 mV
17.998 mV
Содержание UDC 2300
Страница 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Страница 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Страница 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Страница 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Страница 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Страница 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Страница 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Страница 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Страница 177: ......
Страница 178: ......
Страница 180: ......
Страница 181: ......
Страница 182: ......
Страница 183: ......
Страница 184: ......