background image

T4098A,B DELUXE ELECTRIC HEAT THERMOSTATS

68-0146—3

5

Check Calibration

���

Turn the setting knob clockwise until the switch makes
(clicking sound). The heating equipment and fan start.

���

No recalibration is necessary if the thermostat switch
makes with the thermostat setting at the same
temperature as indicated on the thermometer.

���

If the thermostat setting differs from the thermometer,
record the temperature difference and recalibrate as
instructed in the Recalibration Procedure section.

Recalibration Procedure

���

Note the temperature difference between the
temperature setting and the thermometer.

���

Remove the thermostat cover.

���

With the thermostat cover removed, note the location of
the temperature setting knob.

���

Remove the clear plastic knurled setting knob. See
Fig. 5.

���

Turn the temperature setting dial the required number
of degrees for calibration (so thermostat temperature
setting and thermometer are the same).

���

Replace the knob on the setting dial.

���

Replace the thermostat cover and recheck the
calibration.

Setting Range Stops

Use the range stops (included) to limit the maximum and
minimum temperatures that may be set.

���

Move the thermostat setting knob to the desired
maximum temperature.

���

Remove the thermostat cover.

���

Adjust the knob indicator tab between the range stop
positions to prevent interference.

���

Insert the range stop pins in the desired positions on
the back of the thermostat cover. See Fig. 6.

���

Make sure pins are completely seated before replacing
the thermostat cover.

���

Replace the thermostat cover and check the range
stops.

Locking Cover

The thermostat cover may be locked using the locking cover
screws included. Locking the cover prevents unauthorized
tampering of the thermostat temperature setting.

���

Remove the thermostat cover.

���

Insert the locking cover clip (included) into the slot on
the back of thermostat base as shown in Fig. 7.

���

Using an Allen wrench, insert the locking cover screw
into the clip. Secure the screw in place until it is flush
with the thermostat base.

M5793

THERMOSTAT 
BASE

DUAL-DIAPHRAGM
SENSING ELEMENT

SETTING DIAL

CLEAR PLASTIC 
KNURLED
SETTING KNOB

Fig. 5. Calibrating thermostat.

M5800

2

8

24

20

C 16

12

8

0

70

F

60

50

INSIDE VIEW 
OF THERMOSTAT
COVER

INSERT PINS INTO
TEMPERATURE 
STOP POSITIONS.

Fig. 6. Setting range stops.

Содержание T4098A

Страница 1: ...nsive vapor filled dual diaphragm sensing element provides 2 F 1 C sensitivity with minimum droop Replaces virtually all standard wall mounted line voltage thermostats Includes long lasting Micro Switch mechanism Color coded leads allow easy installation Protective cover door opens to provide access to setpoint knob Attractive sloped faceplate allows easy viewing of temperature Classic styling CON...

Страница 2: ...rds Association Performance Certified C273 4 Accessories 272804A Range Stop and Locking Screw Assembly Includes locking cover screws Tinnerman clips wrench and range stops two plastic pins to insert inside cover for field selection of minimum and maximum temperature settings ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor re...

Страница 3: ...lectrical shock or equipment damage 2 If connecting with aluminum conductors use CO ALR solderless wire connectors to avoid fire hazard 3 Do not remove thermostat cover until wiring is complete to avoid damaging the sensing element Location Install a vertical outlet box that is used to mount the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at room temperature Do ...

Страница 4: ...thermostat base with one hand use the other hand to remove the thermostat cover by grasping the bottom cover edge and pulling outward away from the thermostat base Mount the thermostat on the outlet box as shown in Fig 4 Secure the thermostat by tightening the two mounting screws WALL MOUNTING SCREWS 2 M5794 OUTLET BOX THERMOSTAT BASE Fig 4 Mounting thermostat to outlet box New Applications Discon...

Страница 5: ...se the range stops included to limit the maximum and minimum temperatures that may be set Move the thermostat setting knob to the desired maximum temperature Remove the thermostat cover Adjust the knob indicator tab between the range stop positions to prevent interference Insert the range stop pins in the desired positions on the back of the thermostat cover See Fig 6 Make sure pins are completely...

Страница 6: ...setting as necessary OPERATION The T4098 Thermostat provides precise temperature control of resistance rated electric baseboard heating equipment with minimum droop The T4098 controls room temperature within 2 F 1 C regardless of the load of the baseboard heater The vapor filled dual diaphragm sensing element is more sensitive to temperature changes than a bimetal sensor This accuracy usually asso...

Страница 7: ...T4098A B DELUXE ELECTRIC HEAT THERMOSTATS 68 0146 3 7 ...

Страница 8: ...ll Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 68 0146 3 C H Rev 4 96 Printed in U S A Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 Printed on recycled paper containing at least 10 post consumer paper fibers www honeywell com building components ...

Отзывы: