background image

T4098A,B DELUXE ELECTRIC HEAT THERMOSTATS

68-0146—3

2

SPECIFICATIONS

IMPORTANT

The Specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed. For exact
engineering specifications, contact your Honeywell
sales representative.

TRADELINE® Models

TRADELINE® models are selected and packaged to provide
ease of stocking and handling and also maximum
replacement value. See Table 1 for TRADELINE® model
specifications.

Table 1. Thermostat Specifications.

Electrical Ratings (Noninductive Resistive Loads):

22A at 120/208/240 Vac, 60 Hz.
19A at 277 Vac, 60 Hz.

Wiring Connections:
6 in. (150 mm) leads suitable for connecting to aluminum
wiring if approved special service CO/ALR connectors are
used.

Sensing Element:
Vapor-filled dual diaphragm.

Setpoint Adjustment:
Knurled knob on front of thermostat.

Differential:
2

°

F (1

°

C), nonadjustable.

Dimensions:
See Figs. 1 and 2.

Mounting:
Mount directly on vertical 2 x 4 in. outlet box, or on 4 x 4 in.
outlet box using ring adapter (ordered separately).

Approvals:

Underwriters Laboratories Listed: File No. E47434, Guide

No. XAPX.

Canadian Standards Association Listed: File No. LR1322.
Canadian Standards Association Performance Certified:

C273.4.

Accessories:
272804A Range Stop and Locking Screw Assembly. Includes
locking cover screws, Tinnerman clips, wrench, and range
stops—two plastic pins to insert inside cover for field-
selection of minimum and maximum temperature settings.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number or specify.

1. Model number.
2. Switching.
3. Type of finish.

If you have additional questions, need further information or would like to comment on our products or services, please write or
phone:

1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International sales and
service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Model

Number Switching

Temp.

Rating  
F° (C°)

Finish

Includes

T4098A

Spst;
makes
single line
break on
temperature
fall.

50° to 90°
(10° to 30°)

Classic
beige or
Premier
White™

Cover
thermometer,
temperature
range stops,
and locking
cover.

T4098B

Dpst;
makes
double line
break with
setting knob
in OFF
position.

50° to 90°
(10° to 30°)

Classic
beige or
Premier
White™

Cover
thermometer,
temperature
range stops,
and locking
cover.

Содержание T4098A

Страница 1: ...nsive vapor filled dual diaphragm sensing element provides 2 F 1 C sensitivity with minimum droop Replaces virtually all standard wall mounted line voltage thermostats Includes long lasting Micro Switch mechanism Color coded leads allow easy installation Protective cover door opens to provide access to setpoint knob Attractive sloped faceplate allows easy viewing of temperature Classic styling CON...

Страница 2: ...rds Association Performance Certified C273 4 Accessories 272804A Range Stop and Locking Screw Assembly Includes locking cover screws Tinnerman clips wrench and range stops two plastic pins to insert inside cover for field selection of minimum and maximum temperature settings ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor re...

Страница 3: ...lectrical shock or equipment damage 2 If connecting with aluminum conductors use CO ALR solderless wire connectors to avoid fire hazard 3 Do not remove thermostat cover until wiring is complete to avoid damaging the sensing element Location Install a vertical outlet box that is used to mount the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at room temperature Do ...

Страница 4: ...thermostat base with one hand use the other hand to remove the thermostat cover by grasping the bottom cover edge and pulling outward away from the thermostat base Mount the thermostat on the outlet box as shown in Fig 4 Secure the thermostat by tightening the two mounting screws WALL MOUNTING SCREWS 2 M5794 OUTLET BOX THERMOSTAT BASE Fig 4 Mounting thermostat to outlet box New Applications Discon...

Страница 5: ...se the range stops included to limit the maximum and minimum temperatures that may be set Move the thermostat setting knob to the desired maximum temperature Remove the thermostat cover Adjust the knob indicator tab between the range stop positions to prevent interference Insert the range stop pins in the desired positions on the back of the thermostat cover See Fig 6 Make sure pins are completely...

Страница 6: ...setting as necessary OPERATION The T4098 Thermostat provides precise temperature control of resistance rated electric baseboard heating equipment with minimum droop The T4098 controls room temperature within 2 F 1 C regardless of the load of the baseboard heater The vapor filled dual diaphragm sensing element is more sensitive to temperature changes than a bimetal sensor This accuracy usually asso...

Страница 7: ...T4098A B DELUXE ELECTRIC HEAT THERMOSTATS 68 0146 3 7 ...

Страница 8: ...ll Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 68 0146 3 C H Rev 4 96 Printed in U S A Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 Printed on recycled paper containing at least 10 post consumer paper fibers www honeywell com building components ...

Отзывы: