background image

T4098A,B DELUXE ELECTRIC HEAT THERMOSTATS

68-0146—3

4

M5814B

T4098B

ELECTRIC
HEATER

T1

L1

T2

L2

L1 
(HOT)

L2

1

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED.

USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS 
WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE 
HAZARD MAY RESULT.

BREAKS AND REMAKES BELOW -31°F(-35°C); NORMALLY 
THERMALLY ACTIVATED.  BREAKS ON A TEMPERATURE RISE; 
MAKES ON A TEMPERATURE FALL.

USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.

BREAKS AT POSITIVE OFF ONLY; NOT THERMALLY ACTIVATED.

DO NOT CONNECT GROUNDED CONDUCTORS (NEUTRAL)  ON
120V OR 277V CIRCUITS.  INSULATE AND TAPE, OR CUT OFF 
RED WIRES IF UNUSED.

1

2

3

4

5

5

6

6

3

2

4

RED WIRE

Fig. 3. Typical wiring connections for T4098B.

IMPORTANT

If locking cover feature is desired, insert the locking
cover clip in the thermostat base before mounting
the thermostat on the wall. See Fig. 7.

Replacement Applications

���

Disconnect power to thermostat to prevent electrical
shock or equipment damage. All wiring must comply
with local electrical codes and ordinances.

���

Remove the old thermostat from the wall; be careful not
to damage the wiring insulation.

���

Check the old wire insulation for cracks, nicks or fraying.
Apply approved electrical tape to insulate wires or
replace wires as necessary.

���

Do not remove T4098 Thermostat Cover. Using wire
connectors approved for No. 12 wires, make line
voltage connections directly to the leadwires on the
thermostat. See Figs. 2 and 3 for typical wiring
connections.

���

Prebend and push the solid wires into the outlet box.

���

While holding the thermostat base with one hand, use
the other hand to remove the thermostat cover by
grasping the bottom cover edge and pulling outward
away from the thermostat base.

���

Mount the thermostat on the outlet box as shown in
Fig. 4. Secure the thermostat by tightening the two
mounting screws.

WALL 

MOUNTING
SCREWS (2)

M5794

OUTLET
BOX

THERMOSTAT
BASE

Fig. 4. Mounting thermostat to outlet box.

New Applications

���

Disconnect the power supply to prevent electrical shock
or equipment damage. All wiring must comply with local
electrical codes and ordinances.

���

Run the line voltage wiring to the thermostat location.

���

Do not remove the T4098 Thermostat Cover. Using wire
connectors approved for No. 12 wires, make line
voltage connections directly to the leadwires on the
thermostat. See Figs. 2 and 3 for typical wiring
connections.

���

Prebend and push the solid wires into the outlet box.

���

While holding the thermostat base with one hand, use
the other hand to remove the thermostat cover by
grasping the bottom cover edge and pulling outward
away from the thermostat base.

���

Mount the thermostat on the outlet box as shown in
Fig. 4. Secure the thermostat by tightening the two
mounting screws.

SETTINGS AND ADJUSTMENTS

Calibration

The T4098 Thermostats are calibrated at the factory using
precise instruments under closely controlled conditions.
Recalibration should not be necessary. Allow the thermostat
to operate for several hours before checking the calibration.
The T4098 Thermostat vapor-filled dual diaphragm sensing
element is affected by barometric pressure and altitude.
Temperature deviations of 1

°

F (0.5

°

C) are normal. If the

thermostat is mounted in a suitable location (as instructed in
the Location section) and still appears out of calibration,
check calibration as follows.

Содержание T4098A

Страница 1: ...nsive vapor filled dual diaphragm sensing element provides 2 F 1 C sensitivity with minimum droop Replaces virtually all standard wall mounted line voltage thermostats Includes long lasting Micro Switch mechanism Color coded leads allow easy installation Protective cover door opens to provide access to setpoint knob Attractive sloped faceplate allows easy viewing of temperature Classic styling CON...

Страница 2: ...rds Association Performance Certified C273 4 Accessories 272804A Range Stop and Locking Screw Assembly Includes locking cover screws Tinnerman clips wrench and range stops two plastic pins to insert inside cover for field selection of minimum and maximum temperature settings ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor re...

Страница 3: ...lectrical shock or equipment damage 2 If connecting with aluminum conductors use CO ALR solderless wire connectors to avoid fire hazard 3 Do not remove thermostat cover until wiring is complete to avoid damaging the sensing element Location Install a vertical outlet box that is used to mount the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at room temperature Do ...

Страница 4: ...thermostat base with one hand use the other hand to remove the thermostat cover by grasping the bottom cover edge and pulling outward away from the thermostat base Mount the thermostat on the outlet box as shown in Fig 4 Secure the thermostat by tightening the two mounting screws WALL MOUNTING SCREWS 2 M5794 OUTLET BOX THERMOSTAT BASE Fig 4 Mounting thermostat to outlet box New Applications Discon...

Страница 5: ...se the range stops included to limit the maximum and minimum temperatures that may be set Move the thermostat setting knob to the desired maximum temperature Remove the thermostat cover Adjust the knob indicator tab between the range stop positions to prevent interference Insert the range stop pins in the desired positions on the back of the thermostat cover See Fig 6 Make sure pins are completely...

Страница 6: ...setting as necessary OPERATION The T4098 Thermostat provides precise temperature control of resistance rated electric baseboard heating equipment with minimum droop The T4098 controls room temperature within 2 F 1 C regardless of the load of the baseboard heater The vapor filled dual diaphragm sensing element is more sensitive to temperature changes than a bimetal sensor This accuracy usually asso...

Страница 7: ...T4098A B DELUXE ELECTRIC HEAT THERMOSTATS 68 0146 3 7 ...

Страница 8: ...ll Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 68 0146 3 C H Rev 4 96 Printed in U S A Home and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley MN 55422 Printed on recycled paper containing at least 10 post consumer paper fibers www honeywell com building components ...

Отзывы: