Honeywell SmartValve SV9520H Скачать руководство пользователя страница 7

SV9520H SMARTVALVE™ SYSTEM CONTROL LINE VOLTAGE POLARITY SENSE MODELS

7

69-1383

Check and Adjust Gas Input and 
Burner Ignition

CAUTION

Equipment Damage Hazard.
Incorrect inputs can damage equipment and 
produce erroneous readings.

1. Do not exceed input rating stamped on 

appliance nameplate, or manufacturer 
recommended burner orifice pressure for size 
orifice(s) used. Make certain primary air supply 
to main burner is properly adjusted for 
complete combustion. Follow instructions of 
appliance manufacturer.

2. IF CHECKING GAS INPUT BY CLOCKING 

GAS METER: Make certain there is no gas 
flow through the meter other than to the 
appliance being checked. Other appliances 
must remain off with the pilots extinguished (or 
that consumption must be deducted from the 
meter reading). Convert flow rate to Btuh as 
described in form 70-2602, Gas Controls 
Handbook, and compare to Btuh input rating 
on appliance nameplate.

3. IF CHECKING GAS INPUT WITH 

MANOMETER: Make sure the ignition system 
control  is in the OFF position before removing 
outlet pressure tap plug to connect manometer 
(pressure gauge). Also move the ignition 
system control switch to the OFF position 
when removing the gauge and replacing the 
plug. Before removing inlet pressure tap plug, 
shut off gas supply at the manual valve in the 
gas piping to the appliance or, for LP, at the 
tank. Also shut off gas supply before 
disconnecting manometer and replacing plug. 
Repeat Gas Leak Test at plug with main burner 
operating.

NOTE:

Check the inlet pressure before adjusting the 
pressure regulator.

1.

Check the full rate manifold pressure listed on the 
appliance nameplate. Ignition system control full 
rate outlet pressure should match this rating.

2.

With main burner operating, check the ignition 
system control flow rate using the meter clocking 
method or check pressure using a manometer 
connected to the outlet pressure tap on the ignition 
system control. See Fig. 4.

3.

If necessary, adjust the pressure regulator to 
match the appliance rating. See Tables 8A and 8B 
for factory-set nominal outlet pressure and 
adjustment range.
a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise

  to increase or 

counterclockwise

  to decrease the gas 

pressure to the burner.

c. Always replace the cap screw and tighten 

firmly to prevent gas leakage.

4.

If the desired outlet pressure or flow rate cannot be 
achieved by adjusting the ignition system control, 
check the ignition system control inlet pressure 
using a manometer at the ignition system control 
inlet pressure tap. If the inlet pressure is in the 
nominal range (see Tables 7 and 8), replace the 
ignition system control. Otherwise, take the 
necessary steps to provide proper gas pressure to 
the control.

If the burner firing rate is above 150,000 Btuh on SV9520 
models, it may not be possible to deliver the desired 
outlet pressure. This is an application issue, not a control 
failure. Take whatever steps are required to correct the 
situation.

MAINTENANCE

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe
injury, or death.
Do not attempt to take the control apart or clean 
it. Improper cleaning or reassembly can cause 
gas leakage.

Regular preventive maintenance is important in 
applications such as in the commercial cooking and 
agricultural and industrial industries that place a heavy 
load on system controls because:

In many such applications, particularly commercial 
cooking, the equipment operates 100,000 to 200,000 
cycles per year. Such heavy cycling can wear out the 
gas control in one to two years.

Exposure to water, dirt, chemicals and heat can 
damage the gas control and shut down the control 
system. 

Maintenance frequency must be determined individually 
for each application. Some considerations are:

Cycling frequency. Appliances that may cycle 20,000 
times annually should be checked monthly.

Intermittent use. Appliances that are used seasonally 
should be checked before shutdown and again before 
the next use.

Consequence of unexpected shutdown. Where the 
cost of an unexpected shutdown would be high, the 
system should be checked more often.

Dusty, wet, or corrosive environment. Since these 
environments can cause the gas control to deteriorate 
more rapidly, the system should be checked more 
often.

The system should be replaced if:

It does not perform properly on checkout or 
troubleshooting.

The gas control is likely to have operated for more 
than 200,000 cycles.

The control is wet or looks as if it has been wet.

Содержание SmartValve SV9520H

Страница 1: ... control is removed when the thermostat call for heat ends This system is suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 2 for temperature ...

Страница 2: ...pressure drop Table 4 Gas Capacity Conversion Factor Table 5 Adapter Flange Part Numbers a Flange kits include one flange one O ring and four mounting screws PLANNING THE INSTALLATION WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Follow these warnings exactly 1 Plan the installation as outlined below 2 Plan for frequent maintenance as described in the Maintenanc...

Страница 3: ...l Shock Hazard Can cause serious injury or death Disconnect power supply before installation More than one disconnect may be necessary Connect the appliance chassis to earth ground Make sure the 120 Vac neutral line and earth ground are electrically common at the breaker box INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the produc...

Страница 4: ...he control after completing the installation includes leak testing the adapters and screws If you use a wrench on the valve after the flanges are installed use the wrench only on the flange not on the control See Fig 5 Location The SV9520H is mounted in the appliance vestibule on the gas manifold CAUTION Equipment Damage Hazard Water can damage equipment and wiring Do not locate where water can dr...

Страница 5: ...ol inlet and outlet if necessary 6 Connect the pipe to the ignition system control inlet and outlet Use a wrench on the square ends of the ignition system control If a flange is used place the wrench on the flange rather than on the ignition system control Refer to Fig 4 and 5 Fig 4 Top view of ignition system control Fig 5 Proper use of wrench on ignition system control with and without flanges P...

Страница 6: ...commonality STARTUP AND CHECKOUT Ignition System Control Switch Settings Ignition system control switch settings are as follows OFF prevents main gas flow through the ignition system control ON permits gas to flow through the control body At the appropriate time in the appliance operation main gas can flow to the main burner NOTE Controls are shipped with the ignition system control switch in the ...

Страница 7: ...river turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the gas pressure to the burner c Always replace the cap screw and tighten firmly to prevent gas leakage 4 If the desired outlet pressure or flow rate cannot be achieved by adjusting the ignition system control check the ignition system control inlet pressure using a manometer at the ignition system control ...

Страница 8: ...ening model to assure lightoff at step pressure Model Type Type of Gas Nominal Inlet Pressure Range Factory Set Nominal Outlet Pressure Setting Range Step Full Rate Step Full Rate Slow NAT 5 0 to 7 0 3 5 3 0 to 5 0 LP 12 0 to 14 0 10 0 8 0 to 12 0 Model Type Type of Gas Nominal Inlet Pressure Range Factory Set Nominal Outlet Pressure Setting Range Step Full Rate Step Full Rate Slow NAT 1 2 to 1 7 ...

Страница 9: ...ls 3 Observe LED indicator on SV9520 check and repair the system as noted in Table 9 4 After LED flash code analysis and appliance repair are complete turn thermostat below room temperature for 10 seconds turn the thermostat above room temperature to initiate a new call for heat 5 Observe the ignition sequence comparing it to the Sequence of Operation shown in Fig 11 Allow the new ignition sequenc...

Страница 10: ...tion comparing it to the Sequence of Operation shown in Fig 11 Allow the ignition sequence to proceed until the appliance lights or an abnormal or unexpected event is observed Be sure to wait long enough for one of the LED diagnostic codes to flash 7 Observe the LED indicator on the SmartValve check and repair the system as noted in Table 10 8 After analysis and repair are complete turn off applia...

Страница 11: ...reset the safety control 2 Disconnect all electric power to the appliance 3 Remove the ignition system control access panel 4 Move the ignition system control switch to the OFF position 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow Step 1 in the Warning above If you do not smell gas continue with the next step 6 Move the ignition system control switch to the O...

Страница 12: ...R PROVING SWITCH PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE 1 HOUR AUTO LOCKOUT RESET DELAY MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT FAILED TRIALS FOR IGNITION LESS THAN FOUR DURING THIS IGNITION SEQUENCE NO NO YES YES YES NO NO MAIN VALVE ...

Страница 13: ...hes Limit string open Combustion air blower is energized If control system includes ST9160 Electronic Fan Timer the heat speed circulating air fan will be energized System waits for limit string to close then initiates a new ignition sequence 1 Open high temperature or auxiliary limit switch 2 Open manual reset or auto reset burner rollout switch in the limit circuit 3 Limit and rollout switch cir...

Страница 14: ... inducer wiring 2 Low line voltage power supply 3 Airflow proving switch operation tubing wiring 4 Obstructions or restrictions in appliance air intake or exhaust flue system that prevent proper combustion airflow 5 Other devices such as auxiliary limits in the airflow proving circuits 6 4 Flashesa b Soft Lockout Recycle count exceeds 5 on this call for heat last failure was Limit Circuit Opened D...

Страница 15: ...hes Limit string open Combustion air blower is energized If control system includes ST9160 Electronic Fan Timer the heat speed circulating air fan will be energized System waits for limit string to close then initiates a new ignition sequence 1 Open high temperature or auxiliary limit switch 2 Open manual reset or auto reset burner rollout switch in the limit circuit 3 Limit and rollout switch cir...

Страница 16: ... 2 Low line voltage power supply 3 Airflow proving switch operation tubing wiring 4 Obstructions or restrictions in appliance air intake or exhaust flue system that prevent proper combustion airflow 5 Other devices such as auxiliary limits in the airflow proving circuits 6 4 Flashesa b Soft Lockout Recycle count exceeds 5 on this call for heat last failure was Limit Circuit Opened During Run 1 Ope...

Отзывы: