SV9520H SMARTVALVE™ SYSTEM CONTROL LINE VOLTAGE POLARITY SENSE MODELS

11

69-1383

INSTRUCTIONS TO THE HOMEOWNER

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe
 injury, or death.
Follow these warnings exactly:

1. IF YOU SMELL GAS:

Turn off the gas supply at the appliance 
service valve. On LP gas systems, turn off 
the gas supply at the gas tank.

Do not light any appliances in the house.

Do not touch electrical switches or use the 
phone.

Leave the building and use a neighbors 
phone to call your gas supplier.

If you cannot reach your gas supplier, call 
the fire department.

2. The ignition system control must be replaced in 

event of any physical damage, tampering, bent 
terminals, missing or broken parts, stripped 
threads, or evidence of exposure to heat. 

IMPORTANT

Follow the operating instructions provided by 
the manufacturer of your heating appliance. The 
information below describes a typical ignition 
system control application, but the specific 
controls used and the procedures outlined by 
the manufacturer of your appliance can differ, 
requiring special instructions.

STOP: Read the Warnings Above.

If the appliance does not  turn on when the thermostat  is 
set several degrees above room temperature, follow 
these instructions:

1.

Set the thermostat to its lowest setting to reset the 
safety control.

2.

Disconnect all electric power to the appliance.

3.

Remove the ignition system control access panel.

4.

Move the ignition system control switch to the OFF 
position. 

5.

Wait five minutes to clear out any unburned gas. If 
you then smell gas, STOP! Follow Step 1 in the 
Warning above. If you do not smell gas, continue 
with the next step.

6.

Move the ignition system control switch to the ON 
position.

7.

Replace the ignition system control access panel.

8.

Reconnect all electric power to the appliance.

9.

Set the thermostat to the desired setting.

10.

If the appliance does not turn on, move the ignition 
system control switch to the OFF position and 
contact a qualified service technician for 
assistance.

 

Fig. 10. SV9520 typical boiler wiring diagram.

L1

L2

M17609

DATA

R

24V THERMOSTAT

C

R8285D CONTROL CENTER

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION 
AS REQUIRED.

CONNECT THE 120V (HOT) LEAD AS SHOWN.

DATA AND R LINES MUST BE CONNECTED TO AQUASTAT CONTROL FOR PROPER 
SYSTEM OPERATION.

APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND.

IN THIS APPLICATION, POSTPURGE FUNCTION IS NOT AVAILABLE AND THE LED 
FUNCTIONS ONLY DURING A CALL FOR HEAT.

1

2

3

4

5

5

CIRCULATOR

R

C

G

Y

W

1

3

4

6

L2

L1
(HOT)

1

2

3

TO 120 VAC, 60 HZ 
POWER SUPPLY

C1

C2

C3

AIR 
PROVING 
SWITCH

AQUASTAT
CONTROL

NEUTRAL

HOT

ROLL-OUT

SWITCH

LIMIT

SWITCH

COMBUSTION 
AIR BLOWER

AIR

SV9520

HOT 
SURFACE 
IGNITER

FLAME ROD

4

AUXILIARY
LIMIT SWITCH
(OPTIONAL)

1

1

5
6

7
8

3

2

2

2

3

3

1

4

4

4

Содержание SmartValve SV9520H

Страница 1: ... control is removed when the thermostat call for heat ends This system is suitable for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 2 for temperature ...

Страница 2: ...pressure drop Table 4 Gas Capacity Conversion Factor Table 5 Adapter Flange Part Numbers a Flange kits include one flange one O ring and four mounting screws PLANNING THE INSTALLATION WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Follow these warnings exactly 1 Plan the installation as outlined below 2 Plan for frequent maintenance as described in the Maintenanc...

Страница 3: ...l Shock Hazard Can cause serious injury or death Disconnect power supply before installation More than one disconnect may be necessary Connect the appliance chassis to earth ground Make sure the 120 Vac neutral line and earth ground are electrically common at the breaker box INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the produc...

Страница 4: ...he control after completing the installation includes leak testing the adapters and screws If you use a wrench on the valve after the flanges are installed use the wrench only on the flange not on the control See Fig 5 Location The SV9520H is mounted in the appliance vestibule on the gas manifold CAUTION Equipment Damage Hazard Water can damage equipment and wiring Do not locate where water can dr...

Страница 5: ...ol inlet and outlet if necessary 6 Connect the pipe to the ignition system control inlet and outlet Use a wrench on the square ends of the ignition system control If a flange is used place the wrench on the flange rather than on the ignition system control Refer to Fig 4 and 5 Fig 4 Top view of ignition system control Fig 5 Proper use of wrench on ignition system control with and without flanges P...

Страница 6: ...commonality STARTUP AND CHECKOUT Ignition System Control Switch Settings Ignition system control switch settings are as follows OFF prevents main gas flow through the ignition system control ON permits gas to flow through the control body At the appropriate time in the appliance operation main gas can flow to the main burner NOTE Controls are shipped with the ignition system control switch in the ...

Страница 7: ...river turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the gas pressure to the burner c Always replace the cap screw and tighten firmly to prevent gas leakage 4 If the desired outlet pressure or flow rate cannot be achieved by adjusting the ignition system control check the ignition system control inlet pressure using a manometer at the ignition system control ...

Страница 8: ...ening model to assure lightoff at step pressure Model Type Type of Gas Nominal Inlet Pressure Range Factory Set Nominal Outlet Pressure Setting Range Step Full Rate Step Full Rate Slow NAT 5 0 to 7 0 3 5 3 0 to 5 0 LP 12 0 to 14 0 10 0 8 0 to 12 0 Model Type Type of Gas Nominal Inlet Pressure Range Factory Set Nominal Outlet Pressure Setting Range Step Full Rate Step Full Rate Slow NAT 1 2 to 1 7 ...

Страница 9: ...ls 3 Observe LED indicator on SV9520 check and repair the system as noted in Table 9 4 After LED flash code analysis and appliance repair are complete turn thermostat below room temperature for 10 seconds turn the thermostat above room temperature to initiate a new call for heat 5 Observe the ignition sequence comparing it to the Sequence of Operation shown in Fig 11 Allow the new ignition sequenc...

Страница 10: ...tion comparing it to the Sequence of Operation shown in Fig 11 Allow the ignition sequence to proceed until the appliance lights or an abnormal or unexpected event is observed Be sure to wait long enough for one of the LED diagnostic codes to flash 7 Observe the LED indicator on the SmartValve check and repair the system as noted in Table 10 8 After analysis and repair are complete turn off applia...

Страница 11: ...reset the safety control 2 Disconnect all electric power to the appliance 3 Remove the ignition system control access panel 4 Move the ignition system control switch to the OFF position 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow Step 1 in the Warning above If you do not smell gas continue with the next step 6 Move the ignition system control switch to the O...

Страница 12: ...R PROVING SWITCH PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE 1 HOUR AUTO LOCKOUT RESET DELAY MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT FAILED TRIALS FOR IGNITION LESS THAN FOUR DURING THIS IGNITION SEQUENCE NO NO YES YES YES NO NO MAIN VALVE ...

Страница 13: ...hes Limit string open Combustion air blower is energized If control system includes ST9160 Electronic Fan Timer the heat speed circulating air fan will be energized System waits for limit string to close then initiates a new ignition sequence 1 Open high temperature or auxiliary limit switch 2 Open manual reset or auto reset burner rollout switch in the limit circuit 3 Limit and rollout switch cir...

Страница 14: ... inducer wiring 2 Low line voltage power supply 3 Airflow proving switch operation tubing wiring 4 Obstructions or restrictions in appliance air intake or exhaust flue system that prevent proper combustion airflow 5 Other devices such as auxiliary limits in the airflow proving circuits 6 4 Flashesa b Soft Lockout Recycle count exceeds 5 on this call for heat last failure was Limit Circuit Opened D...

Страница 15: ...hes Limit string open Combustion air blower is energized If control system includes ST9160 Electronic Fan Timer the heat speed circulating air fan will be energized System waits for limit string to close then initiates a new ignition sequence 1 Open high temperature or auxiliary limit switch 2 Open manual reset or auto reset burner rollout switch in the limit circuit 3 Limit and rollout switch cir...

Страница 16: ... 2 Low line voltage power supply 3 Airflow proving switch operation tubing wiring 4 Obstructions or restrictions in appliance air intake or exhaust flue system that prevent proper combustion airflow 5 Other devices such as auxiliary limits in the airflow proving circuits 6 4 Flashesa b Soft Lockout Recycle count exceeds 5 on this call for heat last failure was Limit Circuit Opened During Run 1 Ope...

Отзывы: