Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1
7
4.1 Transmitter
The transmitter enclosure has three threaded entries. The two M20 cable entries either
side of the upper part of the transmitter housing are for connecting the power source,
signal output and relay contacts to associated signalling equipment. The bottom M25 entry
allows local mounting of a Sensepoint Toxic sensor or cable entry when using a remotely
mounted sensor. There is a mounting plate incorporated into the transmitter housing
allowing for various mounting configuration options.
A local LCD provides gas type, concentration, alarm and operating status. The display
provides numerical, bar graph and icon information.
Diagnostic information may also be displayed when the transmitter is interrogated using
a magnet. The transmitter cover has a glass window which allows use of the Magnetic
Wand to activate the three user interface magnetic switches that are located on the front
of the display module. The magnet also enables a non intrusive, one-man calibration and
configuration facility for the Sensepoint XCD RTD.
4.2 Sensepoint Toxic Gas Sensor
The Sensepoint XCD RTD transmitter is designed to work with a range of Sensepoint
toxic sensors (see section 7 for details of gases and ranges available) .
Diagram 2: Sensepoint XCD RTD Display and Magnetic Switches
Measuring
Units
Inhibit Icon
Test Pass Icon
Warning/
Fault Icon
Magnetic Wand
activation Icon
Gas Type
Magnetic
MENU/ENTER
Switch
Magnetic
UP Switch
Magnetic
DOWN
Switch
Gas Reading
Bar Graph
Alarm Icon
Full Scale
Calibration Icon
XCD RTD
Содержание Sensepoint XCD RTD
Страница 1: ...Technical Manual Sensepoint XCD RTD Remote Toxic Detector Technical Manual ...
Страница 56: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 56 17 5 Mounting Bracket Drawing ...
Страница 58: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 58 China GB Ex English Version ...
Страница 59: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 59 China PA Certification ...
Страница 60: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 60 18 2 Korea KTL ...
Страница 61: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 61 18 3 European ATEX ATEX For Transmitter ...
Страница 62: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 62 ATEX Original Certificate For Transmitter ...
Страница 63: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 63 ATEX for Sensor ...
Страница 64: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 64 18 4 International IEC IEC Ex for Transmitter ...
Страница 65: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 65 IEC Ex for Sensor ...
Страница 66: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 66 18 5 ATEX Name Plate ...