Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1
28
7. Hold the magnet over (
) for one second and remove. The display will return to ‘SEL
GAS’.
8. Hold the magnet over the (▼) switch twice, the display will show ‘QuIT’. Hold the
magnet over (
) for one second and remove. The XCD RTD will return to normal
Monitoring mode and the new GAS TYPE will be shown on the display.
When using a Honeywell Analytics Sensepoint Toxic sensor, go to section 9.1.2.
9.1.1.1 USER Gas Type set up
When a gas detector other than the Honeywell Analytics Sensepoint Toxic range of
sensors is to be used with XCD RTD, please set the appropriate Unit of Measure from a
pre-selected list and a ‘custom’ Gas Name which may be edited from 4 available alpha-
numeric characters (default is ‘CO’), using the following procedure:
1. Complete steps (1.) to (4.) in section 9.1.1. Untill the LCD shows ‘gAS User’ (the
User part is flashing).
2. Hold the magnet over (
) for one second and remove. The display will show ‘UNIT’
and one of the units of measure will be flashing at the lower right hand side of the
LCD.
3. Now with the magnet, use the (▲) or (▼) switches to scroll (one at a time) through
the available units of measure until the desired one is found. The available units are
listed as below.
Unit of measure
Unit Description
k
Kelvin
A
Ampere
mA
Milli ampere
kppm
Thousands of ppm
mg/m3
milligram per cubic meter
%Vol
Percent volume
ppm
Parts per million
[blank]
When there is no appropriate unit of measure available,
then [blank] can be used. A ‘custom’ unit of measure may be
printed and attached to the instrument manually
4. Hold the magnet over the (
) switch for one second and remove. The display will
then show ‘NAmE CO’ (the first character of ‘CO’ has a flashing cursor under it).
5. Now with the magnet, use the (▼) switch to scroll (one at a time) through the
available alpha-numeric characters until the desired one is found.
6. Hold the magnet over the (▲) switch to move the flashing cursor to the next
Содержание Sensepoint XCD RTD
Страница 1: ...Technical Manual Sensepoint XCD RTD Remote Toxic Detector Technical Manual ...
Страница 56: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 56 17 5 Mounting Bracket Drawing ...
Страница 58: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 58 China GB Ex English Version ...
Страница 59: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 59 China PA Certification ...
Страница 60: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 60 18 2 Korea KTL ...
Страница 61: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 61 18 3 European ATEX ATEX For Transmitter ...
Страница 62: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 62 ATEX Original Certificate For Transmitter ...
Страница 63: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 63 ATEX for Sensor ...
Страница 64: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 64 18 4 International IEC IEC Ex for Transmitter ...
Страница 65: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 65 IEC Ex for Sensor ...
Страница 66: ...Sensepoint XCD RTD Technical Manual SPXCDHMRTEN Issue 1 66 18 5 ATEX Name Plate ...