92
MAN0530 Issue 10 - 11/09
Searchline Excel
2104M0506
Cal sensor
This menu option zeros the system.
Notes:
1.
The 4-20 output is inhibited during this procedure. See the earlier description.
2.
There must be no gas in the system beam path whilst this procedure is carried out.
The following message is displayed:
Ensure Zero Gas
Press Enter
The following message is displayed while the calibration operation is being performed:
Processing Data
Please Wait...
If the calibration is successful, the following message is displayed for a period of three
seconds:
Zero Calibrated
force ma
This option allows the system’s analogue output signal to be adjusted to a fixed level, e.g. when
setting up a system controller. The following message is displayed:
O/P current mA
mmmmm
where:
mmmmm
Current to output.
This is adjusted using the and
keys over the range 1mA to 21mA in steps of 0.1mA.
After adjustment the output is forced to the set level and the following message is displayed:
Fixed: mmmmm mA
Press Enter
where:
mmmmm
Analogue output current previously set.
Normal ma
This menu option returns the system to its normal analogue output state, irrespective of its
previous state. If successful, the following message is displayed for three seconds:
4-20mA Released
>
>
APPENDIX A - HANDHELD INTERROGATOR
Содержание Searchline Excel
Страница 1: ...Searchline Excel Infrared Gas Detectors Technical Handbook ...
Страница 72: ...72 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION 7 2 5 System Diagram ...
Страница 79: ...79 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION ...
Страница 80: ...80 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION With DX100 M Termination Unit ...