23
MAN0530 Issue 10 - 11/09
Searchline Excel
2104M0506
3. INSTALLATION AND OPERATION
3.4 POWER SUPPLY
3.4.1 General
The Searchline Excel gas detector is designed to be operated from a nominal 24V DC supply.
The supply voltage at the terminals must be within the range 18 to 32V.
The unit maximum power consumption and cable lengths are as follows:
Maximum Power Maximum Cable Length
Maximum Cable Length
Consumption (W) (m) with 1.5mm
2
(m) with 2.5mm
2
Unit Type
Conductors (12 ohms/km) Conductors (7.6 ohms/km)
Receiver (All ranges)
8
550
900
SR Transmitter,
5
900
1,400
(Turbo heating enabled)
SR Transmitter,
3.5
1,300
2,000
(Turbo heating disabled)
MR/LR Transmitter,
7.5
600
950
(Turbo heating enabled)
MR/LR Transmitter,
5.5
820
1,300
(Turbo heating disabled)
Notes:
1.
Control room supply voltage assumed to be +24V.
2.
Standard configuration of the Transmitter is with turbo heating enabled.
Terminal sizes: DVC100(M) MK2
0.5mm
2
- 4mm
2
(20AWG - 12AWG)
DX100(M)
0.5mm
2
- 4mm
2
(20AWG - 12AWG)
Honeywell Analytics
Junction Box 00780-A-0100
0.5mm
2
- 6mm
2
(20AWG - 10AWG)
3.4.2 Power Supply Connections - Turbo heating Disabled
When connected as shown in section
3.3.4 Transmitter Connections
all ranges of Transmitter
have turbo heating mode enabled.
This means that during conditions of low ambient temperature, additional heating power is
applied to the unit’s window to minimise condensation, frosting and snow buildup.
If the application/installation does not require turbo heating, reduced power consumption can
be achieved by disabling this mode.
The turbo heating is disabled by reversing the power supply connections to the Transmitter as
shown in the following diagram. All other connections remain the same.
Содержание Searchline Excel
Страница 1: ...Searchline Excel Infrared Gas Detectors Technical Handbook ...
Страница 72: ...72 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION 7 2 5 System Diagram ...
Страница 79: ...79 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION ...
Страница 80: ...80 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION With DX100 M Termination Unit ...