5. PROBLEM SOLVING
Fault/Problem
Causes
Remedies
Diagnostics
Receiver misaligned
1) Re-align the Receiver, first using the
report
telescope and then using the Interrogator.
Neg Gas
2) Re-zero the unit.
reading
Contamination of windows
1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required.
See
Chapter 5
.
2) Re-zero the unit.
Negative drift of unit’s zero
Re-zero the unit.
position
Diagnostics
Receiver misaligned
1) Re-align the Receiver, first using the
report
telescope and then using the Interrogator.
baseline drift
2) Re-zero the unit.
Contamination of windows
1) Check the Transmitter and Receiver
windows for build up of contamination.
Clean windows if required.
2) Re-zero the unit.
Drift of unit’s baseline
Re-zero the unit
Diagnostics
Unit has been operated
1) When Ex certified equipment is
report
at a temperature outside
operated outside its certified range, its
bad
its specified
and certified range
type approval certification is invalidated
temperature
along with its warranty.
Such equipment should be removed from
service in potentially explosive
atmospheres.
2) Investigate the cause of the excessive
temperature excursion and take steps to
prevent recurrence. (e.g. fit sunshade or
heat-shield, or relocate detector, etc.)
Diagnostics
Incorrect supply voltage
1) Check that the +24V supply voltage is
report
reaching unit
reaching the unit
supply fault
(it should be b18V and +32V).
2) Identify the cause of incorrect supply
voltage reaching the unit and rectify.
Diagnostics
Fault on the unit's digital
If this fault is displayed when the unit is
report
PCB
interrogated, it cannot be remedied
dsP fault
in the field.
Diagnostics
A fault has been detected in
If this fault is displayed when the unit is
report
the NV-RAM
interrogated, it cannot be remedied
Nv-ram fault
in the field.
Diagnostics
The time and date record
1) Re-enter the time and date using the
report
being stored by the Real
Interrogator.
rtC fault
Time Clock (RTC) has been
2) Cycle the power applied to the unit.
lost
3) Verify that the time and date record was
maintained after cycling the power.
Diagnostics
Voltage reference fault
If this fault is displayed when the unit is
report
detected
interrogated, it cannot be remedied in the
volt ref fault
field.
Содержание Searchline Excel
Страница 1: ...Searchline Excel Infrared Gas Detectors Technical Handbook ...
Страница 72: ...72 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION 7 2 5 System Diagram ...
Страница 79: ...79 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION ...
Страница 80: ...80 MAN0530 Issue 10 11 09 Searchline Excel 2104M0506 7 CERTIFICATION With DX100 M Termination Unit ...