EXCEL 10 HAND HELD TOOL
Page 35
74-2566
The HHT displays the current value for the MORNING WARM-UP damper position in <%>.(the range is 0 through 100 with a
default of 50%). The operator enters a new value for the MORNING WARM-UP damper position and then presses the Enter
key. The operator has to press the Prev Menu key to get back to the DAMPER POSITIONS Main Menu.
Pressurization
Select the Pressurization menu item from the DAMPER POSITIONS Main Menu and then press the Enter key. The HHT
displays the following screen.
P R E S S U R I Z A T I O N
< % >
The HHT displays the current value for the PRESSURIZATION damper position in <%>.(the range is 0 through 100 with a
default of 100%). The operator enters a new value for the PRESSURIZATION damper position and then presses the Enter
key. The operator has to press the Prev Menu key to get back to the DAMPER POSITIONS Main Menu.
Depressurization
Select the Depressurization menu item from the DAMPER POSITIONS Main Menu and then press the Enter key. The HHT
displays the following screen.
D E P R E S S U R I Z A T I O N
< % >
The HHT displays the current value for the DEPRESSURIZATION damper position in <%>.(the range is 0 through 100 with a
default of 100%). The operator enters a new value for the DEPRESSURIZATION damper position and then presses the Enter
key. The operator has to press the Prev Menu key to get back to the DAMPER POSITIONS Main Menu.
Closed Pos Offset
Select the Closed Pos Offset menu item from DAMPER POSITIONS Main Menu and then press the Enter key. The HHT
displays the following screen.
C L O S E D P O S O F F S E T
< % >
The HHT displays the current value for the CLOSED POSITION OFFSET damper position in <%>(the range is 0 through 100
with a default of 0%). The operator enters a new value for the CLOSED POSITION OFFSET (if the Excel 10 is configured for
a window sensor, the damper uses this value when there is an open window condition) damper and then presses the Enter
key. The operator has to press the Prev Menu key to get back to the DAMPER POSITIONS Main Menu.
Cooling Gains
From the MISCELLANEOUS Main Menu, the operator can select the Cooling Gains menu item and then press the Enter
key. The HHT displays the following screen.