S E L E C T D U C T D I A M E T E R
4
5
6
8
1 0
1 2
1 4
1 6
1 8
2 0
2 2
2 4
2 6
3 0
The operator uses the Up/Down Arrow keys to select the correct Duct Diameter value and then presses the Enter key. The
operator must press the Prev Menu key twice to get back to the PARAMETERS Main Menu.
Motor Speed
Select the Motor Speed menu item from the PARAMETERS Main Menu and then press the Enter key to display the following
MOTOR SPEED screen.
M O T O R S P E E D
< s e c o n d s >
The HHT displays the current value for MOTOR SPEED in <seconds> unless the MOTOR SPEED is equal to zero (the range
is 0 through 600 with a default of 90 seconds). The operator enters a new value for the MOTOR SPEED (the length of time in
seconds that it takes the damper motor to travel one full cycle) and then presses the Enter key. The operator has to press the
Prev Menu key to get back to the PARAMETERS Main Menu.
Valve Speed
Select the Valve Speed menu item from the PARAMETERS Main Menu and then press the Enter key to display the following
VALVE SPEED screen.
NOTE: The Valve Speed menu item is disabled (the speaker beeps and the HHT will not enter this sub-menu) if the Excel
10 controller in not configured for hot water/steam reheat (hw_floating_reheat).
V A L V E S P E E D
< s e c o n d s >
The HHT displays the current value for VALVE SPEED in <seconds> unless the VALVE SPEED is equal to zero (the range is
0 through 255 with a default of 90 seconds). The operator enters a new value for the VALVE SPEED ( the length of time in
seconds that it takes the Valve motor to travel one full cycle and then presses the Enter key. The operator has to press the
Prev Menu key to get back to the PARAMETERS Main Menu.
Frequency Select