EXCEL 10 HAND HELD TOOL
95-2566
34
Miscellaneous
Select the Miscellaneous menu item from the Configuration Main Menu and then press the Enter key. This displays the
following screens containing five sub-menu items.
M I S C E L L A N E O U S
Damper Positions
C o o l i ng G a i n s
R e h e a t G a i n s
Demand Limit Offset
Flow Tracking Offset
Damper Positions
From the MISCELLANEOUS Main Menu, the operator can select the Damper Positions menu item and then press the Enter
key. The HHT displays the following screen.
NOTE: All positions are a percentage of the maximum air flow, unless the operator selects pressure dependent operation
and the setpoints are a percentage of the fully open damper position.
D A M P E R P O S I T I O N S
Night Purge
M o r n i n g W a r m U p
Pressurization
Depressurization
Closed Pos Offset
Night Purge
Select the Night Purge menu item from the DAMPER POSITIONS Main Menu and then press the Enter key. The HHT
displays the following screen.
N I G H T P U R G E
< % >
The HHT displays the current value for the NIGHT PURGE damper position in <%> (the range is 0 through 100 with a default
of 50%). The operator enters a new value for the NIGHT PURGE damper position and then presses the Enter key. The
operator has to press the Prev Menu key to get back to the DAMPER POSITIONS Main Menu.
Morning Warm-up
Select the Morning Warm-up menu item from the DAMPER POSITIONS Main Menu and press the Enter key. The HHT
displays the following screen.
M O R N I N G W A R M - U P
< % >