 4 

2.3 MOUNTING

Mounting dimensions for the transfer switch enclosure are in this 

manual. Enclosures are typically wall-mounted. See “Installation 

Diagram”.

 

 Handle transfer switches carefully when 

installing. Do not drop the switch. Protect 

the switch against impact at all times, and 

against construction grit and metal chips. 

Never install a transfer switch that has been 

damaged.

This transfer switch is mounted in a CSA type 3R enclosure. It can 

be mounted outside or inside and should be based on the layout 

of installation, convenience and proximity to the utility supply and 

load center.
Install the transfer switch as close as possible to the electrical 

loads that are to be connected to it. Mount the switch vertically to 

a rigid supporting structure. To prevent switch distortion, level all 

mounting points. If necessary, use washers behind mounting holes 

to level the unit.

2.4    CONNECTING POWER SOURCE 

AND LOAD LINES

 

 Make sure to turn OFF both the UTILITY 

(NORMAL) and GENERATOR ( STANDBY) 

power supplies before trying to connect 

power source and load lines to the transfer 

switch. Supply voltages are extremely high 

and dangerous. Contact with such high volt-

age power supply lines causes extremely 

hazardous, possibly lethal, electrical shock.

Wiring diagrams and electrical schematics are provided in this 

manual.

NOTE:

All installations must comply with national, state and local 

codes. It is the responsibility of the installer to perform an 

installation that will pass the final electrical inspection.

The utility supply connection is made at the UTILITY SERVICE 

DISCONNECT circuit breaker terminals located in the left side of 

the enclosure. The generator and customer supply load connec-

tions are made at the transfer switch mechanism, located in the 

right side of the enclosure. Each compartment has a neutral lug to 

connect the neutral conductors of each supply and load. A ground 

lug is provided in the right side compartment for connection of the 

ground wires.

The inside cover of the enclosure is split in two sections and 

each side can be accessed independently. It will be necessary 

to remove the inside covers of the enclosure to make the power 

connections to the Utility supply circuit breaker and the transfer 

switch. It will also be necessary to remove the plastic cover over 

the utility supply connections by sliding it perpendicular to the face 

of the circuit breaker.
Conductor sizes must be adequate to handle the maximum cur-

rent to which they will be subjected, based on the 75°C column of 

tables, charts, etc. used to size conductors. The installation must 

comply fully with all applicable codes, standards and regulations.
All power cables must enter the enclosure through the knockouts 

provided. If not using the knockouts, conduit entry into the enclo-

sure must be at or below knockouts to maintain the Type 3R rating. 

Conduits should be arranged to provide separation between the 

Utility and Generator supply conductors inside the enclosure.
Before connecting wiring cables to terminals, remove any surface 

oxides from the cable ends with a wire brush. If ALUMINUM con-

ductors are used, apply corrosion inhibitor to conductors. Tighten 

terminal lugs to the torque values on "Utility Service Disconnect 

Circuit Breaker", and on the decal located on the inside cover. After 

tightening terminal lugs, carefully wipe away any excess corrosion 

inhibitor.

 

 Use a torque wrench to tighten the conduc-

tors, being sure not to overtighten, or dam-

age to the switch base could occur. If not 

tightened enough, a loose connection would 

result, causing excess heat which could 

damage the switch base.

Connect power source load conductors to clearly marked transfer 

mechanism terminal lugs as follows
1.  Connect UTILITY (NORMAL) power source cables to UTILITY 

SERVICE DISCONNECT circuit breaker, neutral wire to neutral 

block.

2.  Connect the GENERATOR (STANDBY) source power cables to 

switch terminals E1, E2, neutral wire to neutral block.

3.  Connect customer LOAD leads to switch terminals T1, T2, 

neutral wire to neutral block.

Conductors must be properly supported, of approved insulative 

qualities, protected by approved conduit, and of the correct wire 

gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal 

parts and grounded metal. Allow at least 1/2 inch for 100-400 

amp circuits.

 

 The plastic cover must be in place and prop-

erly secured in the mounting grooves of 

the Utility circuit breaker after connection 

of supply cables. The inside covers of the 

enclosure must be securely bolted in place 

before either supply source is energized.

Installation

Содержание RTS-CSA

Страница 1: ...This manual should remain with the unit Technical Manual RTS CSA Transfer Switch ...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers due to backfeed of electrical energy Improper or unauthorized installation operation service or repair of the equipment is extremely dangerous and may result in death serious personal injury or ...

Страница 3: ... possible injury that might be caused by such sudden start ups the system s automatic start circuit must be disabled before working on or around the generator or transfer switch Then place a DO NOT OPERATE tag on the transfer switch and on the generator Remove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Equipment Description 2 1 2 ...

Страница 4: ...s not to be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A Utility 6 350 MCM 375 in lbs 200A Load Generator 6 250 MCM 275 in lbs This transfer switch is suitable for control of motors electric dis charge lamps tungsten filament and electric heating equipment where the sum of motor full load ampere rating...

Страница 5: ...facturer recommends that a copy of the SAFETY RULES are posted near the transfer switch Also be sure to read all instructions and information found on tags labels and decals affixed to the equipment Three publications that outline the safe use of transfer switches are the following NFPA 70 National Electrical Code NFPA 70E Standard for Electrical Safety in the Workplace CSA C22 1 Canadian Electric...

Страница 6: ...eaker and the transfer switch It will also be necessary to remove the plastic cover over the utility supply connections by sliding it perpendicular to the face of the circuit breaker Conductor sizes must be adequate to handle the maximum cur rent to which they will be subjected based on the 75 C column of tables charts etc used to size conductors The installation must comply fully with all applica...

Страница 7: ...BEFORE the transfer switch is operated electrically To check manual operation proceed as follows 1 Turn the generator s AUTO OFF MANUAL switch to OFF 2 Turn OFF both UTILITY service disconnect circuit breaker and GENERATOR generator main line circuit breaker power supplies to the transfer switch 3 Note position of transfer mechanism main contacts by observing the moveable contact carrier arm This ...

Страница 8: ...40 246 VAC c Terminals E1 to NEUTRAL 120 123 VAC d Terminals E2 to NEUTRAL 120 123 VAC 8 Set the generator s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre quency are correct and within stated limits If the no load volt age is correct but no load frequ...

Страница 9: ...7 Notes ...

Страница 10: ...8 Installation Diagrams 100 200A non SE ATS Enclosure Drawing No 0H5575 B ...

Страница 11: ...9 100 200A non SE ATS Enclosure Drawing No 0H5575 B Installation Diagrams ...

Страница 12: ...10 Installation Diagrams 100 200A non SE ATS Enclosure Drawing No 0H5573 A ...

Страница 13: ...11 200A Service Entrance ATS Enclosure Drawing No 0H5574 A Installation Diagrams ...

Страница 14: ...LLOWING 1 Costs of normal maintenance adjustments installation and start up 2 Units sold rated or used for Prime Power Trailer Mounted or Rental Unit applications as Generac has defined Prime Power Trailer Mounted or Rental Unit Contact a Generac Distributor for Prime Power Trailer Mounted or Rental Unit definition and warranty 3 Failures caused by any external cause or act of God such as but not ...

Страница 15: ...Ce manuel doit rester avec l unité Manuel technique Commutateur de transfert RTS CSA ...

Страница 16: ...e d alimentation PUBLIQUE NORMALE avec un commutateur de transfert approuvé Ne pas isoler les sources d alimentation normales et de secours de chacune peut entraîner des blessures ou la mort pour les travailleurs des services d électricité due s à la réalimentation de l énergie électrique L installation le fonctionnement l entretien ou la réparation incorrecte ou non autorisée de l équipement est ...

Страница 17: ...in le circuit de démarrage automatique du système désactivé avant de travailler sur ou autour de la génératrice ou du commutateur de transfert Ensuite apposer une étiquette DO NOT OPERATE Ne pas faire fonctionner sur le commutateur de transfert et sur la génératrice Retirer le câble Négatif Nég ou de la batterie Règles de sécurité À l intérieur de la première page Information générale 2 1 1 Introd...

Страница 18: ... Plage Couple 100A 14 1 0 AWG 50 po lb Alimentation électrique de 200 amp 6 350 MCM 375 po lb Génératrice et charge de 200 amp 6 250 MCM 275 po lb Ce commutateur de transfert est adapté pour le contrôle des moteurs des lampes à décharge électrique des équipements de chauffage électrique et à filament de tungstène où la somme de l intensité nominale de la charge totale du moteur et l intensité nomi...

Страница 19: ... copie des RÈGLES DE SÉCURITÉ près du commutateur de transfert S assurer également de lire toutes les instructions et les informations qui se trouvent sur les étiquettes les autocollants et les plaques apposés à l équipement Trois publications décrivant l utilisation sécuritaire des commutateurs de transfert sont les suivantes NFPA 70 National Electrical Code Manuel NFPA du code électrique nationa...

Страница 20: ...cteur de la source publique et au commutateur de transfert Il sera également nécessaire d enlever le couvercle en plastique sur les connexions de la source publique en le faisant glisser perpendiculaire à la face du disjoncteur Les dimensions des conducteurs doivent être suffisantes pour manipuler le courant maximum à laquelle ils seront soumis selon la colonne de 75 C des tableaux graphiques etc ...

Страница 21: ... interrupteur AUTO OFF MANUAL Auto arrêt manuel sur la position OFF Arrêt 2 Mettre en arrêt OFF les sources d alimentation PUBLIQUES disjoncteur pour la déconnexion du service et de la GÉNÉRATRICE disjoncteur principal au commutateur de transfert 3 Remarquer la position des contacts principaux du mécanisme de transfert en observant le bras de support du contact mobile Ceci peut être vu à travers l...

Страница 22: ...gler le disjoncteur principal CB1 de la génératrice sur sa position OFF Arrêt ou OPEN ouvert 9 Régler l interrupteur AUTO OFF MANUAL Auto arrêt manuel sur la position OFF Arrêt pour arrêter la génératrice REMARQUE NE PAS continuer tant que la tension et la fréquence CA de la génératrice sont correctes et dans les limites établies Si la tension à circuit ouvert est appropriée mais la fréquence à ci...

Страница 23: ...7 Remarques ...

Страница 24: ...IQUE PAS AUX ÉLÉMENTS SUIVANTS 1 Les coûts de maintenance ajustements installation et démarrage 2 Les unités vendues classées ou utilisées pour des applications Énergie primaire Montées sur remorque ou Unité en location et définies par Generac comme étant en Énergie primaire Monté sur remorque ou Unité en location Contacter un distributeur Generac pour connaitre la définition d Énergie primaire Mo...

Отзывы: