 6 

3.2.2   CLOSE TO GENERATOR SOURCE SIDE

Before proceeding, verify the position of the switch by observ-

ing the position of the manual operation handle in Figure 3.1. If 

the handle is DOWN, the contacts are closed in the GENERATOR 

(STANDBY) position. No further action is required. If the handle is 

UP, proceed with Step 1.
Step 1:  With the handle inserted into the moveable contact carrier 

arm, move the handle DOWN. Be sure to hold on to the 

handle as it will move quickly after the center of travel.

Step 2:  Remove manual operating handle from moveable contact 

carrier arm. Return handle to storage bracket.

3.2.3   RETURN TO UTILITY SOURCE SIDE

Step 1:  Manually actuate switch to return manual operating handle 

to the UP position.

Step 2:  Remove manual operating handle from moveable contact 

carrier arm. Return handle to storage bracket.

3.3 VOLTAGE 

CHECKS

1.  Turn ON the UTILITY power supply to the transfer switch using 

the UTILITY SERVICE DISCONNECT circuit breaker.

 

 PROCEED WITH CAUTION. THE TRANSFER 

SWITCH IS NOW ELECTRICALLY HOT. 

CONTACT WITH LIVE TERMINALS RESULTS 

IN EXTREMELY HAZARDOUS AND POSSIBLY 

FATAL ELECTRICAL SHOCK.

2.   With an accurate AC voltmeter, check for correct voltage. 

Measure across ATS terminal lugs N1 and N2. Also check N1 

to NEUTRAL and N2 to NEUTRAL.

3.  When certain that UTILITY supply voltage is correct and compat-

ible with transfer switch ratings, turn OFF the UTILITY supply to 

the transfer switch.

4.   On the generator panel, set the AUTO/OFF/ MANUAL switch to 

MANUAL position. The generator should crank and start.

5.   Let the generator stabilize and warm up at no-load for at least 

five minutes.

6.   Set the generator's main circuit breaker (CB1) to its ON or 

CLOSED position.

 

 PROCEED WITH CAUTION. GENERATOR 

OUTPUT VOLTAGE IS NOW BEING 

DELIVERED TO TRANSFER SWITCH 

TERMINALS. CONTACT WITH LIVE 

TERMINALS RESULTS IN EXTREMELY 

DANGEROUS AND POSSIBLY FATAL 

ELECTRICAL SHOCK.

7.   With an accurate AC voltmeter and frequency meter, check the 

no-load, voltage and frequency.

 

Measure across ATS terminal lugs E1 to E2. Also check E1 to 

NEUTRAL and E2 to NEUTRAL.

 a. Frequency 

....................................................60-62 

Hertz

  b.  Terminals E1 to E2 .......................................240-246 VAC
  c.  Terminals E1 to NEUTRAL ............................120-123 VAC
  d.  Terminals E2 to NEUTRAL ............................120-123 VAC

8.  Set the generator’s main circuit breaker (CB1) to its OFF or 

OPEN position.

9.  Set the AUTO/OFF/MANUAL switch to the OFF position to shut 

down the generator.

NOTE:

Do NOT proceed until generator AC output voltage and fre-

quency are correct and within stated limits. If the no-load volt-

age is correct but no-load frequency is incorrect, the engine 

governed speed may require adjustment. If no-load frequency 

is correct but voltage is not, the voltage regulator may require 

adjustment.

3.4  

GENERATOR TESTS UNDER 
LOAD

1.  Set the generator's main circuit breaker to its OFF or OPEN 

position.

2.  Set the UTILITY SERVICE DISCONNECT circuit breaker to the 

OFF position.

3.  Manually actuate the transfer switch main contacts to 

their GENERATOR (STANDBY) position. Refer to "Manual 

Operation".

4.  To start the generator, set the AUTO/OFF/ MANUAL switch to 

MANUAL. When engine starts, let it stabilize for a few min-

utes.

5.  Turn the generator's main circuit breaker to its ON or CLOSED 

position. The generator now powers all LOAD circuits. Check 

generator operation under load as follows:

  •   Turn ON electrical loads to the full rated wattage/amper-

age capacity of the generator. DO NOT OVERLOAD.

  •   With maximum rated load applied, check voltage and 

frequency across transfer switch terminals E1 and E2. 

Voltage should be greater than 230VAC and frequency 

should be greater than 59 Hertz.

  •   Let the generator run under rated load for at least 30 min-

utes. With unit running, listen for unusual noises, vibra-

tion, overheating, etc., that might indicate a problem.

6.  When checkout under load is complete, turn the generator's 

main circuit breaker to its OFF or OPEN position.

7.  Let the generator run at no-load for several minutes. Then, 

shut down by setting the AUTO/OFF/MANUAL switch to its 

OFF position.

8.  Move the transfer switch's main contacts back to their UTIL-

ITY position. For example, LOAD connected to UTILITY power 

supply. Refer to "Manual Operation". Handle and operating 

lever of transfer switch should be in the UP position.

9.  Turn on the utility power supply to transfer switch, using the 

UTILITY SERVICE DISCONNECT circuit breaker. The utility 

power source now powers the loads.

10.  Set the generator's AUTO/OFF/MANUAL switch to its AUTO 

position.

Operation

Содержание RTS-CSA

Страница 1: ...This manual should remain with the unit Technical Manual RTS CSA Transfer Switch ...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers due to backfeed of electrical energy Improper or unauthorized installation operation service or repair of the equipment is extremely dangerous and may result in death serious personal injury or ...

Страница 3: ... possible injury that might be caused by such sudden start ups the system s automatic start circuit must be disabled before working on or around the generator or transfer switch Then place a DO NOT OPERATE tag on the transfer switch and on the generator Remove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Equipment Description 2 1 2 ...

Страница 4: ...s not to be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A Utility 6 350 MCM 375 in lbs 200A Load Generator 6 250 MCM 275 in lbs This transfer switch is suitable for control of motors electric dis charge lamps tungsten filament and electric heating equipment where the sum of motor full load ampere rating...

Страница 5: ...facturer recommends that a copy of the SAFETY RULES are posted near the transfer switch Also be sure to read all instructions and information found on tags labels and decals affixed to the equipment Three publications that outline the safe use of transfer switches are the following NFPA 70 National Electrical Code NFPA 70E Standard for Electrical Safety in the Workplace CSA C22 1 Canadian Electric...

Страница 6: ...eaker and the transfer switch It will also be necessary to remove the plastic cover over the utility supply connections by sliding it perpendicular to the face of the circuit breaker Conductor sizes must be adequate to handle the maximum cur rent to which they will be subjected based on the 75 C column of tables charts etc used to size conductors The installation must comply fully with all applica...

Страница 7: ...BEFORE the transfer switch is operated electrically To check manual operation proceed as follows 1 Turn the generator s AUTO OFF MANUAL switch to OFF 2 Turn OFF both UTILITY service disconnect circuit breaker and GENERATOR generator main line circuit breaker power supplies to the transfer switch 3 Note position of transfer mechanism main contacts by observing the moveable contact carrier arm This ...

Страница 8: ...40 246 VAC c Terminals E1 to NEUTRAL 120 123 VAC d Terminals E2 to NEUTRAL 120 123 VAC 8 Set the generator s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre quency are correct and within stated limits If the no load volt age is correct but no load frequ...

Страница 9: ...7 Notes ...

Страница 10: ...8 Installation Diagrams 100 200A non SE ATS Enclosure Drawing No 0H5575 B ...

Страница 11: ...9 100 200A non SE ATS Enclosure Drawing No 0H5575 B Installation Diagrams ...

Страница 12: ...10 Installation Diagrams 100 200A non SE ATS Enclosure Drawing No 0H5573 A ...

Страница 13: ...11 200A Service Entrance ATS Enclosure Drawing No 0H5574 A Installation Diagrams ...

Страница 14: ...LLOWING 1 Costs of normal maintenance adjustments installation and start up 2 Units sold rated or used for Prime Power Trailer Mounted or Rental Unit applications as Generac has defined Prime Power Trailer Mounted or Rental Unit Contact a Generac Distributor for Prime Power Trailer Mounted or Rental Unit definition and warranty 3 Failures caused by any external cause or act of God such as but not ...

Страница 15: ...Ce manuel doit rester avec l unité Manuel technique Commutateur de transfert RTS CSA ...

Страница 16: ...e d alimentation PUBLIQUE NORMALE avec un commutateur de transfert approuvé Ne pas isoler les sources d alimentation normales et de secours de chacune peut entraîner des blessures ou la mort pour les travailleurs des services d électricité due s à la réalimentation de l énergie électrique L installation le fonctionnement l entretien ou la réparation incorrecte ou non autorisée de l équipement est ...

Страница 17: ...in le circuit de démarrage automatique du système désactivé avant de travailler sur ou autour de la génératrice ou du commutateur de transfert Ensuite apposer une étiquette DO NOT OPERATE Ne pas faire fonctionner sur le commutateur de transfert et sur la génératrice Retirer le câble Négatif Nég ou de la batterie Règles de sécurité À l intérieur de la première page Information générale 2 1 1 Introd...

Страница 18: ... Plage Couple 100A 14 1 0 AWG 50 po lb Alimentation électrique de 200 amp 6 350 MCM 375 po lb Génératrice et charge de 200 amp 6 250 MCM 275 po lb Ce commutateur de transfert est adapté pour le contrôle des moteurs des lampes à décharge électrique des équipements de chauffage électrique et à filament de tungstène où la somme de l intensité nominale de la charge totale du moteur et l intensité nomi...

Страница 19: ... copie des RÈGLES DE SÉCURITÉ près du commutateur de transfert S assurer également de lire toutes les instructions et les informations qui se trouvent sur les étiquettes les autocollants et les plaques apposés à l équipement Trois publications décrivant l utilisation sécuritaire des commutateurs de transfert sont les suivantes NFPA 70 National Electrical Code Manuel NFPA du code électrique nationa...

Страница 20: ...cteur de la source publique et au commutateur de transfert Il sera également nécessaire d enlever le couvercle en plastique sur les connexions de la source publique en le faisant glisser perpendiculaire à la face du disjoncteur Les dimensions des conducteurs doivent être suffisantes pour manipuler le courant maximum à laquelle ils seront soumis selon la colonne de 75 C des tableaux graphiques etc ...

Страница 21: ... interrupteur AUTO OFF MANUAL Auto arrêt manuel sur la position OFF Arrêt 2 Mettre en arrêt OFF les sources d alimentation PUBLIQUES disjoncteur pour la déconnexion du service et de la GÉNÉRATRICE disjoncteur principal au commutateur de transfert 3 Remarquer la position des contacts principaux du mécanisme de transfert en observant le bras de support du contact mobile Ceci peut être vu à travers l...

Страница 22: ...gler le disjoncteur principal CB1 de la génératrice sur sa position OFF Arrêt ou OPEN ouvert 9 Régler l interrupteur AUTO OFF MANUAL Auto arrêt manuel sur la position OFF Arrêt pour arrêter la génératrice REMARQUE NE PAS continuer tant que la tension et la fréquence CA de la génératrice sont correctes et dans les limites établies Si la tension à circuit ouvert est appropriée mais la fréquence à ci...

Страница 23: ...7 Remarques ...

Страница 24: ...IQUE PAS AUX ÉLÉMENTS SUIVANTS 1 Les coûts de maintenance ajustements installation et démarrage 2 Les unités vendues classées ou utilisées pour des applications Énergie primaire Montées sur remorque ou Unité en location et définies par Generac comme étant en Énergie primaire Monté sur remorque ou Unité en location Contacter un distributeur Generac pour connaitre la définition d Énergie primaire Mo...

Отзывы: