background image

69-0669B—2

4

3. Check indicator light. If light is on, stray light is falling

on the cad cell or the cad cell is shorted. Correct the problem
to ensure that the light is off before proceeding to the next
step.

4. Open hand valve in oil supply line.
5. Set limit control, and set thermostat to call for heat or

jumper T1-T2 terminals on R8991 to call for heat.

6. After a one second delay, oil burner and ignitor should

turn on.

7. If oil primary control locks out before fuel reaches

burner, push in and release red reset button. The oil burner
should start again after a short delay.

8. Reset R8991 until fuel reaches burner and lights off.

When the burner lights off, the R8991 indicator light should
be on. Do not continuously hold in reset button. The R8991
must sense that reset switch contacts are open and then
closed to allow the control to reset. This prevents a short in
the switch from bypassing the manual reset requirement.

CHECK SAFETY FEATURES
Simulate flame failure:

1. Turn on the main burner by following the starting

procedure.

2. Close hand valve in oil supply line.
3. Observe that oil burner should shut off after oil in

supply line is all used. Oil primary control goes into recycle.
The indicator light flashes at 1/4 Hz (2 seconds on, 2 sec-
onds off). After 60 second recycle time,  another trial for
ignition begins and flashing stops.

4. Observe that oil primary control should lock out within

timing indicated on label. Indicator light should be flashing
at 2 Hz (1/4 second on, 1/4 second off). Ignition and burner
should stop.

Simulate power failure:

1. Turn on the main burner by following the starting

procedure.

2. Disconnect power by switching breaker or removing

fuse. Main burner should shut off.

3. Reconnect power by switching breaker or replacing

fuse. Main burner should turn on after one second.

If the system does not operate as described, proceed to

the Troubleshooting section.

NOTE: The R8991 locks out when eight consecutive trials

for ignition are initiated but not completed (thermostat
closes for less than the lockout time and oil does not
ignite). This prevents an intermittent signal at the thermo-
stat terminals from indefinitely cycling the relay and
restarting the lockout timing.

Troubleshooting

IMPORTANT: Only a trained, experienced service techni-

cian should perform the troubleshooting procedure.

To completely troubleshoot an oil burner installation,

check the burner and oil primary control (which includes
ignition source and cad cell) for proper operation and
condition.

The indicator light on the oil primary control provides

lockout, recycle, and cad cell indication as follows:

Flashing at 2 Hz (1/4 second on, 1/4 second off): System

is locked out.

Flashing at 1/4 Hz (2 seconds on, 2 seconds off): Control

is in the recycle mode.

On: Cad cell is sensing flame.
Off: Cad cell is not sensing flame.

PRELIMINARY STEPS

CAUTION

To prevent damage to the R8991, do not use an
ignition tester to check out the R8991 Ignition
Source. Iron core transformer ignition testers can
damage solid state ignitors.

CAUTION

When using R8991 with a 24V thermostat, dis-
connect at least one lead wire from the T1-T2 ter-
minals on R8991 before jumpering T1-T2 to
simulate a call for heat or damage to thermostat
heat anticipator can result.

Before checking the R8991, perform these preliminary

checks (repair or replace controls as necessary):

• Check the power supply, all wiring connections, and

burner motor fuse. Assure power is turned on to all
controls and burner motor.

• Check the limit switch for proper operation.
• Check the electrode gap and position.
• Check contacts between the R8991 and the electrodes.
• Check the oil pump pressure.
• Check the piping to the oil tank.
• Check the oil nozzle, oil supply, and oil filter.

CHECK OIL PRIMARY CONTROL AND IGNITOR

If the trouble does not seem to be in the burner or

ignition hardware, check the oil primary control and the
ignitor by using the following equipment:

• Screwdriver.
• Voltmeter (0 to 150 Vac).
• Insulated jumper wires with both ends stripped.

CAUTION

Troubleshooting is done with the system powered.
Be careful to observe all necessary precautions to
prevent electrical shock or equipment damage.

BURNER MOTOR DOES NOT START WHEN
THERMOSTAT CALLS FOR HEAT
Preliminary Checks

1. Make sure limit switches are closed and contacts are

clean.

2. Check for line voltage power at the oil primary con-

trol. With thermostat calling for heat, voltage should be
120 Vac between black and white lead wires on oil primary
control.

Содержание R8991

Страница 1: ...nition Recycle Oil Primary and Ignitor consists of an interrupted ignition oil primary solid state ignition source and cad cell flame sensor for mounting directly on an oil burner housing This single unit control primary and ignitor operates the oil burner and oil valve if desired in response to a call for heat from the thermo stat The R8991 monitors the burner flame and shuts down the system on i...

Страница 2: ...ROLLER WIRING CODE LOW VOLTAGE LINE VOLTAGE LINE VOLT THERMOSTAT IF USED BLACK WHITE ORANGE L1 HOT L2 LINE 24V THERMOSTAT 1 2 2 M814 LIMIT BURNER MOTOR OIL VALVE T T R8991 TYPICAL R8991 CONTROL CIRCUIT Operation R8991 Interrupted Ignition Recycle Oil Primary and Ignitor operation is discussed in Table 1 The R8991 Primary and Ignitor is controlled by a small computer This computer determines the ap...

Страница 3: ...et button The green diagnostic light stops flashing and goes off If there is a call for heat the R8991 returns to a try for ignition External Action R8991 Action Connect line voltage power R8991 is energized if limit switch is closed There is no call for heat Green diagnostic light is on if cad cell senses flame Green light is off if cad cell does not sense flame Thermostat calls for heat R8991 do...

Страница 4: ...indefinitely cycling the relay and restarting the lockout timing Troubleshooting IMPORTANT Onlyatrained experiencedservicetechni cian should perform the troubleshooting procedure To completely troubleshoot an oil burner installation check the burner and oil primary control which includes ignition source and cad cell for proper operation and condition The indicator light on the oil primary control ...

Страница 5: ...Turns On Indicator Light Stays Off 3 Check indicator light after flame is established but before oil primary control locks out 3 Indicator light is on until the control locks out Indicator light starts flashing during lockout Oil primary control is defective replace control 3 Indicator light does not turn on Check cad cell sighting for view of flame go to step 4 Burner Locks Out Burner Keeps Runni...

Страница 6: ...and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A www honeywell com QUALITY IS KEY ...

Страница 7: ...ICATIONS Temps de mise sous sécurité 15 30 ou 45 secondes Temps de répétition de cycle 60 secondes Temps de rémanence 45 secondes HOMOLOGATIONS Composants reconnus par les Laboratoires des assureurs Inc dossier MP286 guide MCCZ2 Certifié par l Association canadienne de normalisation dossier no LR95329 1 CARACTÉRISTIQUES ÉLECTRIQUES NOMINALES Entrée 120 V c a 60 Hz Sortie Contacts du moteur du brûl...

Страница 8: ...LORSQUE LE SYSTÈME COMPORTE UN RÉGULATEUR TENSION SECTEUR PLACER UN CAVALIER AUX BORNES T T ET RACCORDER LE THERMOSTAT TENSION SECTEUR EN SÉRIE AVEC LE LIMITEUR 2 S assurer que les connexions tension secteur sont conformes à l illustration de la Fig 2 Raccorder le fil orange au moteur du brûleur le fil blanc à la tension secteur neutre et le fil noir à la tension secteur sous tension 3 Épisser les...

Страница 9: ...manence puis s éteint Le brûleur est en marche La demande de chaleur du thermostat est satisfaite Le brûleur cesse de fonctionner Le voyant s éteint Le brûleur ne s allume pas lors de la demande de chaleur Le moteur du brûleur et l allumeur cessent de fonctionner à la fin du délai de mise sous sécurité a Le brûleur s allume mais la flamme s éteint avant la mise sous sécurité Le voyant vert s étein...

Страница 10: ...ation d alimentation en mazout 5 Régler le limiteur et régler le thermostat pour provoquer un appel de chaleur ou placer un cavalier entre les bornes T1 et T2 du R8991 pour simuler un appel de chaleur 6 Après une seconde le brûleur et l allumeur devrait se mettre en marche 7 Si le régulateur primaire se met sous sécurité avant le mazout n atteigne le brûleur appuyer sur le bouton de réarmement et ...

Страница 11: ...t le filtre VÉRIFIER LE RÉGULATEUR PRIMAIRE DE MAZOUT ET L ALLUMEUR Si le problème ne provient par du brûleur ou du matériel d allumage vérifier le régulateur primaire de mazout et l allumeur au moyen du matériel ci dessous Tournevis Voltmètre 0 à 150 V c a Cavalier isolé dénudé aux deux extrémités AVERTISSEMENT Le système est alimenté en courant lors du dépannage Prendre toutes les précautions né...

Страница 12: ...pas Vérifier la visée de la cellule photoélectrique pour s assurer que la flamme est bien en vue passer à l étape 4 Le brûleur se met sous sécurité Le brûleur continue sans cesse de fonctionner 4a Débrancher l alimentation tension secteur et ouvrir l interrupteur tension secteur 4b Déconnecter la cellule photoélectrique et la nettover en utilisant un linge doux Vérifier la visée et s assurer que l...

Отзывы: