ID3000 Series Installation & Commissioning Manual
Installation Guide
5
997-274-000-6, Issue 6
September 2009
2.2 Pre-installation Check List
Before installing the ID3000 equipment or fitting sensors,
you must first ensure that the following criteria have been
met. Failure to do this may not only result in damage to
the equipment, but may also cause problems when
commissioning the equipment or adversely affect its
performance.
2.2.1 Some DO’s and DON’T’s
Before selecting a location for the control panel and
devices, DO make sure that:
a. The operating ambient temperature is in the
recommended range:
5
°
C to 35
°
C
and
b. The relative humidity is between:
5% and 95%
c. The panel is wall mounted in a position which allows
clear visibility of displays and easy access to operating
controls. The height above floor level should be chosen
such that the LCD is just above normal eye level
(approximately 1.5 metres)
d. DO NOT locate the panel where it is exposed to high
levels of moisture
e. DO NOT locate the panel where there are high levels
of vibration or shock
1.5m