ID3000 Series Installation & Commissioning Manual
A4 - 4
997-274-000-6, Issue 6
September 2009
Appendix 4
3
Installation
One ID
2
net Network Gateway Module (NGM) is
required for each fire control panel. Installation
instructions are provided
with
it. The manual
provides all necessary ID
2
net configuration
instructions. Connection of conventional,
copper-conductor cables are made at this PCB.
If optical-fibre cables are to be used, an interface
PCB is required which is fitted adjacent to the
NGM PCB and connects to it via a short ribbon
cable (refer to
Section 3.1.2
).
3.1 Hardware Requirements
For ID3000 Series control panels - the ID
2
net
NGM PCB and Fibre-optic Interface PCB are
fitted in the panel’s main chassis enclosure.
3.1.1 Network Gateway Module PCB
The Network Gateway Module (NGM) PCB
(PN: 124-312) must be fitted on the right-hand
side of the main chassis enclosure. It plugs
directly into the Processor PCB. For details on
fitting the NGM PCB, setting the network
configuration jumper links and connecting
external cables, refer to instruction sheet (ref.
997-449-000-X) supplied with it.
Note:
Ensure jumper link is fitted at JP7.
3.1.2 Fibre-optic Interface PCB
The Fibre-optic Interface PCB (PN: 124-319) is
only required where optical-fibre cables are being
used. For details on fitting the Fibre-optic
Interface PCB and setting jumper links, refer to
instruction sheet ref. 997-450-000-X supplied
with it.
Note:
Reference to the NGM PCB instruction
sheet (ref. 997-449-000-X) will be required
for correct jumper link setting when using
optical-fibre cables.
See Note