ID3000 Series Installation & Commissioning Manual
Inst
allation - Panel Electronics
26
997-274-000-6, Issue 6
September 2009
5.5 Zonal LED & Printer Options
The section describes the procedures for fitting zonal
LED modules and the integral PRN-ID printer. One or
two extension chassis are required to provide the zonal
LEDs required with or without the integral printer. The
following options are described in this section:
a.
LEDs for up to 64 Zones
. For panels with up to 64
zonal LEDs follow the instructions in
Section 5.5.1
.
b.
LEDs for up to 128 Zones
(as ‘LEDs for up to 64
zones’ x2, with a double-extended back box).
c.
Fitting the PRN-ID Printer
. The integral PRN-ID printer
can only be fitted with the extended or double-extended
back boxes. An extension chassis is required, either with
zonal LEDs 1-64 or with a blank fascia if these zonal LEDs
are not required. Refer to
Section 5.5.2
.
d.
LEDs for up to 256 Zones
. For panels with up to 256
zonal LEDs refer to
Section 5.5.3
. For this option the double-
extended back box and 256 Zone LED Kit is required.
Note:
All fitting instructions assume that the correct back
box option has been installed in each case.
Taking suitable anti-static precautions, such as wearing
a grounded wrist strap, remove all packaging and inspect
for any damage that may have occurred in transit. If no
damage is evident, proceed with these instructions.
5.5.1 64 Zone LED Extension Chassis
Before attempting this procedure, make sure ALL
power to the control panel is disconnected.
Fit the extension chassis (A) to the back box (B) as
follows:
1
Locate the four supplied M4 x 16 SEM screws (C) in the
back box holes (D) and insert them approximately half way.
2
Connect one end of the supplied, 10-way ribbon cable
(E) to the top connector (F), marked ‘IN’, of the LED PCB
(also refer to the drawing overleaf).
3
Connect one end of the supplied earth lead (G) to the
earthing blade terminal (H) on the extension chassis.
4
With the extension chassis correctly orientated (refer
to drawing at left), locate the keyholes onto the four
screws with the threaded part in contact with the top
flats of the keyholes.
5
With the extension chassis now located on the back
box, open the main chassis front door and connect
the other end of the 10-way ribbon cable at socket
SK19 on the Base PCB.
6
Connect the other end of the earth lead to the earthing
blade terminals located inside the back box and to the
right of the chassis.
CAUTION!
Make sure ALL power to
the panel has been
disconnected.
Up to 128 Zones plus
PRN-ID Printer
Up to 256 Zones