ML6984, ML7984 SERIES 4000 DIRECT COUPLED VALVE ACTUATORS

9

95C-10939—11

OPERATION

Each time actuator terminals T5 and T6 are (re)powered, 
the microprocessor will cycle the valve through a full stroke 
to calibrate its position. Any stroke between 1/2 in. (13 
mm) and 1 in. (25 mm) will be divided into 30 equal steps. 
Run time is proportional to stroke length and power supply 
voltage. The actuator will also slow down as the valve 
closes off the seat. The LED lights when terminals T5 and 
T6 are powered, and flashes when the actuator is in motion. 
T5 is connected to Terminal R in ML6984 and to Terminal 
W in ML7984. 

NOTE:

Initial calibration does not apply to ML6984 
installed for 3-wire control or installed for 5-wire 
control without the 272630D position feed-
back/auxiliary switch module. Span and start 
positions will need to be set during controller set-
up. See ML6984 Operation 3-wire, below. ML7984 
always conducts a self-calibration sequence when 
(re)powering up. 

ML7984 Operation 

The microprocessor responds to the signal across the input 
terminals based on the configuration DIP switch settings. 

When correctly connected to the actuator, a control signal 
between signal input terminals is converted to a digital run 
time and compared to pulse counts from the first gear in 
the gear train. When these counters are equal, the drive 
motor and drive shaft are stationary. 

As long as the value of the controlled medium remains at 
the controller setpoint, the control loop circuit is in 
balance, and the actuator does not run. When the 
controller set point or controlled temperature changes, the 
controller output voltage is changed, causing the counters 
to differ. As the actuator moves in the direction to correct 
the difference, the counters increment or decrement, and 
stop the actuator when the input and gear counts agree. 

At the end of the valve stroke, the actuator develops the 
necessary force for positive valve close-off. The motor 
stops automatically when the motor draws a 
predetermined current which corresponds to a force level. 
The digital counters are reset and calibrated at each end of 
stroke. 

Modulating actuators will automatically travel to the 
position corresponding to analog input signal following the 
self-calibration cycle.

CAUTION

Disconnect power supply before beginning 
installation to prevent electrical shock and 
equipment damage. 

All wiring must comply with applicable local 
electrical codes, ordinances, and regulations. 

Make certain that the voltage and frequency of the 
power supply correspond to the rating of the device.

DO NOT electrically operate the MLx984 actuator 
before assembly to the valve because damage not 
apparent to the installer may occur. 

DO NOT connect 24 Vac between any ML7984 
signal input terminals. DEVICE FAILURE WILL 
RESULT. 

NOTE:

1.

The ML7984 must be field configured with the 
DIP switches which are located beside the ter-
minal block. See wiring diagrams for details. 
Turn power off before setting any DIP switches. 

2.

There is a 1.5 second delay in actuator 
response to every signal change. This occurs to 
screen out electrical noise. 

3.

For proper operation, voltage on the T5 and T6 
must not be less than 22 Vac or 24 Vdc during 
running or force generating stages. Increase 
transformer VA rating or use a model with better 
regulation if voltage drops below 22 Vac when 
the valve is closing off. 

ML6984 Floating Operation, 5-Wire 

The motor is controlled by a microprocessor. Connecting B 
to R for 1/10 second or longer tells the microprocessor to 
cause the actuator to drive upwards. Connecting W to R will 
cause the actuator to drive downwards. For “floating” 
control, the actuator will remain in the last position when 
there is no connection to R. 

At the end of the valve stroke, the actuator will develop the 
necessary force for positive valve close-off. As forces are 
developed, the current to the motor increases. The 
microprocessor stops the actuator automatically when 
motor current and force reaches the factory-calibrated 
level. 

NOTE:

There must be at least 1.5 second delay between 
successive floating input signals. The actuator will 
ignore floating signals during calibration cycle 
and does not remember any pulses sent during 
this period. The controller may need to run 
through its own calibration cycle before use. 

ML6984 Operation, 3-Wire 

ML6984 may be installed like a conventional (non-
electronic) floating actuator. The interface electronics are 
powered at the same time as the motor. Pulses must be at 
least 100 ms long with a delay of at least 1500 ms between 
pulses. When ML6984 is not powered between terminals 
T6 and T5/R, self-calibration will not occur. The controller 
must drive the valve through a cycle manually to calibrate 
stroke to the controller. 

Содержание ML6984

Страница 1: ... supply for multiple actuators and controllers 24 Vac or 28 Vdc power supply Field addable position feedback auxiliary switch module available for 5 wire models APPLICATION The ML6984 and ML7984 are self contained self adjusting motorized valve actuators that mount directly onto V5011 two way and V5013 three way globe valves providing linear stem operation between 1 2 in 13 mm and 1 in 25 mm ML698...

Страница 2: ...istance Electrical Ratings Power supply consumption 24 V 10 15 50 60 Hz or 28 Vdc 10 6 VA Run ning 12 VA Valve seating CE Certified Inputs ML6984 25 mA 24 Vac 5 wire mode only 500 mA valve seating 3 wire mode Minimum Signal Input Duration 100 ms ML7984 2 10 Vdc 1 mA 4 20 mAdc May be used with 0 10 Vdc input but valve will be closed at 2 Vdc Input Impedance for the ML7984 Voltage Source 20 KW ohm C...

Страница 3: ...lations Honeywell assumes no responsibility for damages or injuries resulting from non compliance with installation instructions or standard good practice when mounting operating or maintaining the valves even if not explicitly mentioned in the installation instructions Observe all safety practices when working with steam systems Mounting 1 Ensure that valve body is installed correctly arrow point...

Страница 4: ... age the threads or other parts of the stem 4 Orient the conduit hole to the most desirable direc tion then tighten the LOCKNUTS on the U bolt 5 Remove the plastic cover from the MLx984 by loos ening the two captive screws located on the top Drop the Allen Hex type of set screw included in the plas tic bag into the top of the shaft hex side up 6 Tighten the set screw to lock valve stem in place Fi...

Страница 5: ... CAN SHARE SAME TRANSFORMER PROVIDED THAT THE VA RATING OF THE TRANSFORMER IS NOT EXCEEDED AND PROPER PHASING IS OBSERVED DO NOT MIX A C AND D C POWER SOURCES CONTROLLER CAN BE LOW VOLTAGE SPDT SERIES 20 ON OFF OR SP3T SERIES 60 FLOATING TRI STATE TYPE TERMINALS R AND T5 ARE CONNECTED INSIDE THE ML6984 1 2 3 1 2 3 M25493A 3 1 3 W R B T6 T5 C H ML6984 TYPICAL ELECTRONIC CONTROLLER L1 L2 POWER SUPPL...

Страница 6: ...EM MOVES UPWARDS WITH SIGNAL INCREASES TO 10V 20MA ALWAYS TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES 1 2 3 4 5 3 2 1010 10 2 VDC REVERSE ACTING 3 2 3 2 M25496A T5 T6 L1 L2 28 VDC ML7984 R W C T5 T6 OR SIGNAL SOURCE C R W T5 T6 ML7984 ML7984 SLAVE R W C T5 T6 24 VAC FUNCTION DIP SWITCH CONFIGURATION X000 4 20 MA DIRECT ACTING X010 20 4 MA REVERSE ACTING 1 2 3 4 ON 1 OFF 0 1 2 3 4 ON 1 OFF 0 POW...

Страница 7: ...SELECT DEVICE FUNCTIONS DIRECT ACTING FUNCTION ACTUATOR STEM MOVES UPWARDS WITH SIGNAL INCREASE OR REVERSE ACTING FUNCTION ACTUATOR STEM MOVES DOWNWARDS WITH SIGNAL INCREASE 5 TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES FOR COMMON TRANSFORMER AND COMMON CONTROLLER APPLICATION PLEASE CONSULT THE FACTORY 6 MAXIMUM RESISTANCE PER CONTROL CIRCUIT OF 280 OHM M25497A B R W T6 T5 B R W B R W T6 T5 B R...

Страница 8: ...ES TO 10V 20MA OR REVERSE ACTING FUNCTION ACTUATOR STEM MOVES DOWNWARDS WITH SIGNAL INCREASES TO 10V 20MA 5 TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES R W R W M25499A T6 T5 B R W ML7984 T6 T5 B R W L1 L2 OR 28 VDC 24 VAC T5 T6 ML7984 ML7984 T6 T5 B R W R W ELECTRONIC SERIES 90 W973 T775 H775 W7100 NOTE POLARITY SENSITIVE CHECK CONNECTIONS W to R R to W L1 L2 L1 L2 OR OR 28 VDC T5 T6 28 VDC T5 ...

Страница 9: ...nect power supply before beginning installation to prevent electrical shock and equipment damage All wiring must comply with applicable local electrical codes ordinances and regulations Make certain that the voltage and frequency of the power supply correspond to the rating of the device DO NOT electrically operate the MLx984 actuator before assembly to the valve because damage not apparent to the...

Страница 10: ...base between terminals Rc and Y This is needed for electrical compatibility with ML6984 but may result in wider room temperature swings due to the loss of anticipation REPLACEMENT NOTES Fig 18 ML6984 with Honeywell T87K Round Thermostat See Fig 19 if connecting TH5110D or TH6110D FocusPRO thermostats to ML6984 Configure the thermostats for Series 20 operation Fig 19 ML6984 with FocusPro Electronic...

Страница 11: ...endent output switch is needed wire the 2 10 Vdc position feedback signal to an Approved adjustable voltage controlled relay CHECKOUT ML7984 1 Make sure the valve stem is completely screwed into the actuator drive shaft with no threads showing before applying power 2 Make sure the valve stem is locked in place with the set screw 3 Make sure the Configuration DIP switches are set correctly 4 With 2...

Страница 12: ...P switch settings Check against Product Instruction Sheet Noisy Motor Bearing failed due to overheat 1 Check for excessive temperature and replace complete actuator 2 Use high temperature kit 43196000 001 Brushes worn out Check for excessive cycling and replace actuator Motor overheats smoke component burn out Current sensing circuit failed or electronic components failed Replace actuator Make sur...

Отзывы: