ML6984, ML7984 SERIES 4000 DIRECT COUPLED VALVE ACTUATORS

11

95C-10939—11

To Replace ML784 or ML984

1.

The old ML784 or ML984 actuators cannot be used 
with new ML7984 valve actuators in the same cir-
cuitry, unless the old models are each powered by 
their own transformer to prevent cross-talking. 

2.

The ML7984 is a direct replacement for all old 
ML784 and ML984, except: 
a. When replacing the old reverse acting models, the 

signal input wires to the new devices no longer 
need to be reversed. Just follow the terminal 
polarity designations and DIP switch settings. 

b. When replacing the old actuator which has an 

Electronic Series 90 “Supermod” controller - e.g.: 
T775, W973, H775, or W7100 - the old interface 
resistor must be removed. The ML7984 Series 
4000 will work directly with the controller without 
the external 240 ohm resistor. 

c. When replacing the old ML784 (mA model) in 

multiple-actuator installations, resistor(s) will be 
needed. Use Resistor Kit (part no. 272822) and 
set DIP switches accordingly. See Figures 17 and 
18. 

To Replace ML684A 

1.

The new ML6984 is a direct replacement for the old 
ML684A in single actuator or parallel multiple actua-
tors hook-up. The old and new actuators can be 
mixed in the same electrical circuit. For multiple 
actuators controlled by a common controller in paral-
lel, these actuators must be wired so that they all 
travel in the same direction. 

2.

When replacing the ML684A1009 (80 lbf) with this 
new ML6984 on the V5045 valve, the installed valve 
adaptor (part no. 272629A) on the valve stem and 
actuator assembly is still needed. 

NOTE:

The 272630D position feedback/auxiliary switch 
module cannot be used with ML6984 3-wire 
installation. The 272630D requires continuous 
power. 

To Replace ML6874 

1.

The ML6984 is a direct replacement for the old 
ML6874 in single actuator hook-up. 

2.

For parallel, multiple ML6874 actuators applications, 
an isolation relay must be used. The isolation relay 
contacts should be placed in the new ML6984 actua-
tor signal input “W” and “B” circuit. 

To Replace Line Voltage Auxiliary 
Switches 

These accessories are no longer available. Replace the old 
actuator with new model and 272630D position feedback/ 
auxiliary switch module. 

Operate an external relay, such as R8845U, using the 
adjustable SPDT pilot duty output on the 272630D. 

If a second, independent output switch is needed, wire the 
2-10 Vdc position feedback signal to an Approved, 
adjustable, voltage-controlled relay. 

CHECKOUT

ML7984 

1.

Make sure the valve stem is completely screwed into 
the actuator drive shaft with no threads showing 
before applying power. 

2.

Make sure the valve stem is locked in place with the 
set screw. 

3.

Make sure the Configuration DIP switches are set 
correctly. 

4.

With 24 Vac or 28 Vdc power source connected to T5 
and T6, actuator operation can be verified by con-
necting appropriate control signal (Series 70/90) 
from controller to the signal input terminals (Figures 
8 thru 16). For direct acting: A modulating action can 
be obtained by increasing the control signal. The 
actuator will travel from stem down to stem up. On 
signal failure (disconnected/no signal), actuator 
defaults to closed position. For reverse acting: 
Decreasing controller signal will drive actuator from 
full stem down to full stem up. On signal failure (dis-
connect/no signal), actuator defaults to open posi-
tion. 

5.

Operate the system (valve, actuator, and controller) 
for several cycles to ensure proper installation. 

6.

When checkout is complete, return the controller to 
the desired setting. 

NOTE:

1.

The Device will ignore any input changes until it 
has completed its repositioning relative to the 
initial signal input. 

2.

272630D position feedback/auxiliary switch 
module is inactive during self-calibration. 

ML6984: 5-Wire Installation 

1.

Make sure the valve stem is completely screwed into 
the actuator drive shaft with no threads showing 
before applying power. 

2.

Make sure the valve stem is locked in place with the 
set screw. 

3.

Connect 24 Vac or 28 Vdc power to T5 and T6. 

4.

Jumper R and B. The valve stem should move up. 

5.

Jumper R and W. The valve stem should move down. 

6.

For Floating operation, open R connection Valve stem 
should remain in position. 

7.

Re-connect all control wiring. 

8.

Operate the system (valve, actuator, and controller) 
for several cycles to ensure proper installation. 

9.

When checkout is complete, return the controller to 
the desired setting. 

ML6984: 3-Wire Installation

1.

Make sure the valve stem is completely screwed into 
the actuator drive shaft with no threads showing 
before applying power. 

2.

Make sure the valve stem is locked in place with the 
set screw. 

3.

Connect 24 Vac to T6. 

4.

Manually override the controller to signal the actua-
tor to open/close for a few cycles to ensure proper 
installation. 

5.

When checkout is complete, return the controller to 
the desired setting. 

Содержание ML6984

Страница 1: ... supply for multiple actuators and controllers 24 Vac or 28 Vdc power supply Field addable position feedback auxiliary switch module available for 5 wire models APPLICATION The ML6984 and ML7984 are self contained self adjusting motorized valve actuators that mount directly onto V5011 two way and V5013 three way globe valves providing linear stem operation between 1 2 in 13 mm and 1 in 25 mm ML698...

Страница 2: ...istance Electrical Ratings Power supply consumption 24 V 10 15 50 60 Hz or 28 Vdc 10 6 VA Run ning 12 VA Valve seating CE Certified Inputs ML6984 25 mA 24 Vac 5 wire mode only 500 mA valve seating 3 wire mode Minimum Signal Input Duration 100 ms ML7984 2 10 Vdc 1 mA 4 20 mAdc May be used with 0 10 Vdc input but valve will be closed at 2 Vdc Input Impedance for the ML7984 Voltage Source 20 KW ohm C...

Страница 3: ...lations Honeywell assumes no responsibility for damages or injuries resulting from non compliance with installation instructions or standard good practice when mounting operating or maintaining the valves even if not explicitly mentioned in the installation instructions Observe all safety practices when working with steam systems Mounting 1 Ensure that valve body is installed correctly arrow point...

Страница 4: ... age the threads or other parts of the stem 4 Orient the conduit hole to the most desirable direc tion then tighten the LOCKNUTS on the U bolt 5 Remove the plastic cover from the MLx984 by loos ening the two captive screws located on the top Drop the Allen Hex type of set screw included in the plas tic bag into the top of the shaft hex side up 6 Tighten the set screw to lock valve stem in place Fi...

Страница 5: ... CAN SHARE SAME TRANSFORMER PROVIDED THAT THE VA RATING OF THE TRANSFORMER IS NOT EXCEEDED AND PROPER PHASING IS OBSERVED DO NOT MIX A C AND D C POWER SOURCES CONTROLLER CAN BE LOW VOLTAGE SPDT SERIES 20 ON OFF OR SP3T SERIES 60 FLOATING TRI STATE TYPE TERMINALS R AND T5 ARE CONNECTED INSIDE THE ML6984 1 2 3 1 2 3 M25493A 3 1 3 W R B T6 T5 C H ML6984 TYPICAL ELECTRONIC CONTROLLER L1 L2 POWER SUPPL...

Страница 6: ...EM MOVES UPWARDS WITH SIGNAL INCREASES TO 10V 20MA ALWAYS TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES 1 2 3 4 5 3 2 1010 10 2 VDC REVERSE ACTING 3 2 3 2 M25496A T5 T6 L1 L2 28 VDC ML7984 R W C T5 T6 OR SIGNAL SOURCE C R W T5 T6 ML7984 ML7984 SLAVE R W C T5 T6 24 VAC FUNCTION DIP SWITCH CONFIGURATION X000 4 20 MA DIRECT ACTING X010 20 4 MA REVERSE ACTING 1 2 3 4 ON 1 OFF 0 1 2 3 4 ON 1 OFF 0 POW...

Страница 7: ...SELECT DEVICE FUNCTIONS DIRECT ACTING FUNCTION ACTUATOR STEM MOVES UPWARDS WITH SIGNAL INCREASE OR REVERSE ACTING FUNCTION ACTUATOR STEM MOVES DOWNWARDS WITH SIGNAL INCREASE 5 TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES FOR COMMON TRANSFORMER AND COMMON CONTROLLER APPLICATION PLEASE CONSULT THE FACTORY 6 MAXIMUM RESISTANCE PER CONTROL CIRCUIT OF 280 OHM M25497A B R W T6 T5 B R W B R W T6 T5 B R...

Страница 8: ...ES TO 10V 20MA OR REVERSE ACTING FUNCTION ACTUATOR STEM MOVES DOWNWARDS WITH SIGNAL INCREASES TO 10V 20MA 5 TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES R W R W M25499A T6 T5 B R W ML7984 T6 T5 B R W L1 L2 OR 28 VDC 24 VAC T5 T6 ML7984 ML7984 T6 T5 B R W R W ELECTRONIC SERIES 90 W973 T775 H775 W7100 NOTE POLARITY SENSITIVE CHECK CONNECTIONS W to R R to W L1 L2 L1 L2 OR OR 28 VDC T5 T6 28 VDC T5 ...

Страница 9: ...nect power supply before beginning installation to prevent electrical shock and equipment damage All wiring must comply with applicable local electrical codes ordinances and regulations Make certain that the voltage and frequency of the power supply correspond to the rating of the device DO NOT electrically operate the MLx984 actuator before assembly to the valve because damage not apparent to the...

Страница 10: ...base between terminals Rc and Y This is needed for electrical compatibility with ML6984 but may result in wider room temperature swings due to the loss of anticipation REPLACEMENT NOTES Fig 18 ML6984 with Honeywell T87K Round Thermostat See Fig 19 if connecting TH5110D or TH6110D FocusPRO thermostats to ML6984 Configure the thermostats for Series 20 operation Fig 19 ML6984 with FocusPro Electronic...

Страница 11: ...endent output switch is needed wire the 2 10 Vdc position feedback signal to an Approved adjustable voltage controlled relay CHECKOUT ML7984 1 Make sure the valve stem is completely screwed into the actuator drive shaft with no threads showing before applying power 2 Make sure the valve stem is locked in place with the set screw 3 Make sure the Configuration DIP switches are set correctly 4 With 2...

Страница 12: ...P switch settings Check against Product Instruction Sheet Noisy Motor Bearing failed due to overheat 1 Check for excessive temperature and replace complete actuator 2 Use high temperature kit 43196000 001 Brushes worn out Check for excessive cycling and replace actuator Motor overheats smoke component burn out Current sensing circuit failed or electronic components failed Replace actuator Make sur...

Отзывы: