LCBS CONNECT SOLUTION
6
3
1
0
—
S
F
E
8
1
1
0
0
-
1
3
8. Three Heat Three Cool Multispeed Fan with Variable Frequency Drive
MCR36715
COOL 2
FAN MOTOR
COOL 3
COOL 2
COOL 1
M
ANALOG
COMMON
Φ
1
HEAT 2
HEAT 3
HEAT 1
VARIABLE
FREQUENCY
DRIVE
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
24VAC CO
M
24VDC
24VAC
R
W
1
W
2
W
3 O
B
G-L
Y1
Y2
Y3
G-L
RH
RC
CO
M
AU
X
DO
1 AUX
G
UI-1
DI-2
DI-3
UI-4
UI-5
UI-6
UI-2
UI-3
COM
COM
COM
DI-4
DI-1
COM
AO-3
AO-1
COM
AO-2
COM
NET-1
NET-2
S-BUS
S-BUS
SHIELD
EGND
LCBS
CONTROLLER
SYLK BUS
24 VAC
CONTROLLER
POWER
LCBS
CONTROLLER
WALL
MODULE
HVAC SYSTEM
24 VAC POWER
EXISTING
TRANSFORMER
C7250A
MIXED AIR SENSOR
C7250A
DISCHARGE AIR SENSOR
C7400S
RETURN AIR ENTHALPY SENSOR
M7215A
ECONOMIZER ACTUATOR
AT40
TRANSFORMER(S)
THIS APPLICATION PROVIDES AUTOMATIC CONTROL OF THREE STAGES OF DIRECT EXPANSION COOLING AND
INTEGRATED ECONOMIZER WITH DIFFERENTIAL ENTHALPY CONTROL AND HIGH TEMPERATURE LIMIT (SEE
APP GUIDE FOR DETAILED SEQUENCE). CONFIGURER HAS THE ABILITY TO SET UP SETBACK, SETUP FEATURES
THAT WILL ENABLE BUILDING OWNER TO ACHIEVE ENERGY SAVINGS BY REDUCING FAN AND COOLING
EQUIPMENT OPERATION DURING UNOCCUPIED PERIODS. ADAPTIVE INTELLIGENT RECOVERY IS ALSO A
STANDARD FEATURE. IT PERMITS CONTROLLED OPERATIONAL TRANSITION OF COOLING EQUIPMENT FROM
UNOCCUPIED TO OCCUPIED TO 1] GUARD AGAINST EQUIPMENT OVERUSE AND 2] HELP CONTROL POTENTIAL
ELECTRICAL SPIKES RESULTING IN DEMAND CONTROL UTILITY CHARGES. MULTISPEED FAN OPTION PERMITS
CUSTOMIZED CONTROL OF FAN SPEED AND CAN BE INDEXED TO SPECIFIC MODES. THERE ARE SIX MODES
THAT INDIVIDUAL FAN SPEEDS CAN BE COUPLED WITH. SUCCESSFULLY IMPLMEMENTED, COMFORT WITH
ENERGY COST AVOIDANCE IS A PROBABLE OUTCOME.
LCBS CONNECT – INFORMATION
OS#
DESCRIPTION
YCRL6438SR LCBS CONTROLLER (WITH WALL MODULE)
LCBS CONNECT – COMPONENTS SHOWN
C7400S
OUTDOOR AIR ENTHALPY SENSOR
C7250A
MA SENSOR
C7250A
DA SENSOR
C7250A
OA SENSOR
0-10 VDC
Φ
2
Φ
3
Φ
1
Φ
2
Φ
3
BUILDING NAME
CVAHU RTU NAME
DATE
THREE COOL THREE HEAT MULTISPEED FAN WITH VARIABLE FREQUENCE DRIVE