LCBS CONNECT SOLUTION
31-00118EFS—01
28
INDOOR
HUMIDITY
•
•
RETURN AIR RELATIVE HUMIDITY (RH). THIS CAN
BE OF INTEREST TROUBLESHOOTING COOLING
ISSUES. USE "TERMINAL LOAD, ZONE DEMAND"
ALERTING FIRST.
INDOOR
TEMPERATURE
•
•
•
SPACE TEMPERATURE. CAN BE INTERESTING
TROUBLESHOOTING HEATING AND COOLING
ISSUES. USE "TERMINAL LOAD, ZONE DEMAND"
ALERTING FIRST.
COMPRESSOR
CURRENT
TRANSFORMER
SENSOR
•
•
INDICATES COMPRESSOR CURRENT IN AMPS
WHEN THE INPUT UI6 IS CONFIGURED TO
MEASURE COMPRESSOR CURRENT
DISCHARGE AIR
TEMPERATURE
•
•
•
DISCHARGE AIR TEMPERATURE IS A FAVORITE
DIAGNOSTIC TOOL BY MANY HAVE SERVICE
CONTRACTORS. IT IS EASY TO TELL IF THERE IS A
LOW AND DEGRADING DELTA T ACROSS A
COOLING COIL THAT THERE IS SOMETHING
WRONG WITH COOLING SYSTEMS. CONSIDER
ZONE DEMAND AND LOW LIMIT FIRST.
FAN CURRENT
TRANSFORMER
SENSOR
•
•
INDICATES FAN CURRENT IN AMPS WHEN THE
INPUT UI6 IS CONFIGURED TO MEASURE FAN
CURRENT. USEFUL TO MONITOR RELATIVE LOAD
OF FAN. ALSO CAN BE USED TO DETECT HARD
START OF THE LOAD, I.E. EXCESSIVE AMP DRAW.
FILTER STATIC
PRESSURE
•
•
•
INDICATES THE PRESSURE DROP ACROSS THE
FILTER WHEN THE INPUT UI5 IS CONFIGURED TO
MEASURE FILTER PRESSURE. THIS INPUT CAN
BE USED TO MONITOR AND MEASURE FILTER
STATIC, FILTER LOAD. LIMIT CAN BE SET TO
INDICATE WITH FILTER USE BECOMES
INEFFECTIVE.
MIXED AIR
TEMPERATURE
•
•
•
MIXED AIR TEMPERATURE IS A USEFUL
ALERTING POINT TO SERVICE ECONOMIZER USE.
THIS SENSOR IS ALSO "ENTERING SYSTEM
TEMPERATURE." AND IS NECESSARY FOR MOST
UPCOMING HEATING AND COOLING ANALYTICS.
CONSIDER LOW LIMIT FIRST.
OUTDOOR AIR
ENTHALPY
•
OUTDOOR AIR ENTHALPY CAN BE USED TO
TROUBLESHOOT ECONOMIZER ISSUES.
OUTDOOR AIR
HUMIDITY
•
•
OUTDOOR AIR RELATIVE HUMIDITY (RH) CAN BE
USED TO TROUBLESHOOT ECONOIMZER
ISSUES.
OUTDOOR
TEMPERATURE
•
•
•
OUTDOOR AIR TEMPERATURE CAN BE USED TO
TROUBLESHOOT ECONOMIZER ISSUES.
MONITOR
SENSOR 1
•
•
•
WHEN THE INPUT UI5 IS CONFIGURED TO
"MONITOR SENSOR", THIS INDICATES THE VALUE
READ BY THE SENSOR. THIS IS A 0-10 VDC
SENSOR.
MONITOR
SENSOR 2
•
•
•
WHEN THE INPUT UI6 IS CONFIGURED TO
"MONITOR SENSOR", THIS INDICATES THE VALUE
READ BY THE SENSOR. THIS IS A 0-10 VDC
SENSOR.
MONITOR
TEMPERATURE
•
•
•
WHEN THE INPUT UI2 IS CONFIGURED TO
"MONITOR TEMPERATURE", THIS INDICATES THE
VALUE READ BY THE SENSOR. THIS IS A TEMP
SENSOR
Table 6.
SENSOR NAME
DIGITAL
ALERTS
HI LIMIT
ALERTS
LOW LIMIT
ALERTS
SENSOR
FAIL
ALERT
DESCRIPTION AND USE CASES