LCBS CONNECT SOLUTION
27
31-00118EFS—01
ALERTING DETAILS
The following alerts can be activated for the "Alpha Version" of LCBS Connect. This description indicates what the alert is,
how the alert can be used, and what the application benefits are for the alert.
Each Alert can be set up to send messages to service contractor owners, service managers, dispatchers, and technicians
via SMS to Droid and IOS devices. A customized message can be set up in SMS environment, not to exceed 40 characters.
Customized messages can be set up in e-mail format with limitless message format.
Table 6.
SENSOR NAME
DIGITAL
ALERTS
HI LIMIT
ALERTS
LOW LIMIT
ALERTS
SENSOR
FAIL
ALERT
DESCRIPTION AND USE CASES
DIRTY FILTER
DIGITAL
•
INDICATES THE STATE OF THE DIRTY FILTER
DIGITAL INPUT. THIS IS A DIGITAL SIGNAL AND
COUNTS ON SERVICE CONTRACTOR SELECTING
A DIGITAL FLOW SWITCH THAT MEASURES
ENTERING AND LEAVING AIR ACROSS AIR FILTER.
PROOF OF
AIRFLOW DIGITAL
•
INDICATES THE CURRENT STATE OF THE FAN
STATUS DIGITAL INPUT. THIS IS A DIGITAL SIGNAL
AND COUNTS ON SERVICE CONTRACTOR
SELECTING A DIGITAL FLOW SWITCH THAT
MEASURES ENTERING AND LEAVING AIR
ACROSS THE SUPPLY FAN.
FREEZE STAT
•
INDICATES THE STATE OF THE FREEZE STAT
DIGITAL INPUT. ALSO CALLED COIL FREEZE. IF
THIS CONDITION IS DETECTED, LCBS
CONTROLLER LOGIC WILL SHUT OFF SUPPLY
FAN.
USER
CONFIGURED
INPUT
•
MONITOR SWITCH: INDICATES THE STATE OF
THE MONITOR SWITCH DIGITAL INPUT. UP TO
CONFIGURER'S IMAGINATION AND ALERTING
REQUIREMENTS.
RETURN AIR
ENTHALPY
•
•
RETURN AIR ENTHALPY. THIS CAN BE OF
INTEREST TO SERVICE CONTRACTORS WHO MAY
NEED TO TROUBLESHOOT DIFFERENTIAL
ECONOMIZER ISSUES. ALSO CAN BE OF
INTEREST TROUBLESHOOTING COOLING
ISSUES.
RETURN AIR
HUMIDITY
•
•
RETURN AIR RELATIVE HUMIDITY (RH). THIS CAN
BE OF INTEREST TROUBLESHOOTING COOLING
ISSUES.
RETURN AIR
TEMPERATURE
•
•
RETURN AIR TEMPERATURE. ALWAYS
INTERESTING COMPARING RETURN AIR
TEMPERATURE TO ROOM TEMPERATURE.
SHOULD BE ROUGHLY THE SAME ON ONLY
SLIGHTLY OFFSET.
INDOOR CO2
•
•
SPACE CO2 IF DEMAND CONTROLLED
VENTILATION APPLIED, THIS IS AN INTERSTING
POINT TO ALERT.
TERMINAL LOAD,
ZONE DEMAND
•
THIS VERSITLE VALUE INDICATES TRUE HEAT
LOAD IN A SPACE. IT TELLS THE SERVICE
CONTRACTOR IF COOLING AND HEATING
SYSTEMS ARE MEETING BUILDING LOAD. IF THIS
PARAMETER GETS OUT OF CONTROL (130+
COOLING, 130- HEATING; +162 MAX,-162 MIN)
SYSTEMS ARE NOT PERFORMING PROPERLY.