LCBS CONNECT SOLUTION
31-00118EFS—01
30
APPENDIX, WIRING DIAGRAMS
1. Master Points List - Configurable and Fixed Function Points
2. Master Application Inventory - All Wiring Diagrams
UI1
MIXED AIR SENSOR
UI2
OUTDOOR AIR, USER SELECTED MONITOR POINT (20K)
UI3 DISCHARGE
AIR
SENSOR
UI4
CO2 SENSOR
UI5
FILTER PRESSURE, USER SELECTED MONITOR SENSOR 1 (NEED TO SCALE)
UI6
FILTER PRESSURE, COMPRESSOR CURRENT SENSOR, FAN CURRENT SENSOR, USER SELECTED MONITOR SENSOR 2 (NEED TO
SCALE)
DI1
OCCUPANCY, MOTION SENSOR
DI2
PULSE METER
DI3
FREEZE STAT, DIRTY FILTER
DI4
PROOF OF AIRFLOW, USER SELECTED MONITOR SWITCH
AO1
ECONOMIZER ACTUATOR
AO2
ACCESSORY LOOP MODULATING, ACCESSORY LOOP STAGE (NEED RELAY), ACCESSORY LOOP AUX MODULATING
AO3
MULTI -SPEED FAN, ACCESSORY LOOP MODULATING, ACCESSORY LOOP STAGE (NEED RELAY), ACCESSORY LOOP AUX
MODULATING
DO1
OCCUPANCY, ECONOMIZER POWER, SIMPLE DEHUMIFICATION, ACCESSORY LOOP STAGE, ACCESSORY LOOP AUX CONTROL POINT
DO2
HEAT 1
DO3
HEAT 2
DO4
HEAT 3, REVERSING VALVE O OR B, LOW SPEED FAN
DO5
SUPPLY FAN
DO6
COOL 1
DO7
COOL 2
DO8
COOL 3, LOW SPEED FAN
MASTER POINTS LIST THOSE IN
RED
ARE FIXED TO SINGLE INPUT OR OUTPUT DEFINITION
I/O
NAME OF INPUT OUTPUT POINT(S)
MCR36706
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
24VAC CO
M
24VDC
24VAC
R
W1
W2
W
3 O
B
G-L
Y1
Y2
Y3
G-L
RH
RC
CO
M
AU
X
DO
1 AUX
G
UI-1
DI-2
DI-3
UI-4
UI-5
UI-6
UI-2
UI-3
COM
COM
COM
DI-4
DI-1
COM
AO-3
AO-1
COM
A0-2
COM
NET-1
NET-2
S-BUS
S-BUS
SHIELD
EGND
SYLK BUS
24 VAC
CONTROLLER
POWER
LCBS CONNECT – INFORMATION
OS#
DESCRIPTION
YCRL6438SR LCBS CONTROLLER (WITH WALL MODULE)
LCBS
CONTROLLER
LCBS
CONTROLLER
WALL
MODULE
BUILDING NAME
CVAHU RTU NAME
DATE
COOL 2
HEAT 1
HEAT 2
FAN
COOL 2
COOL 1
HVAC SYSTEM
24 VAC POWER
EXISTING
TRANSFORMER
C7250A
MA SENSOR
C7250A
DA SENSOR
C7400S SYLK OUTSIDE AIR
ENTHALPY SENSOR
C7400S SYLK RETURN AIR
ENTHALPY SENSOR
M7215A
ECONOMIZER
ACTUATOR
P7640A
PRESSURE
SENSOR
(IN WC,VDC)
HVAC SYST
DRY CONTACT
24 VAC 1 AMP
MASTER APPLICATION INVENTORY
ACTUATOR
24 VAC POWER
ER
THIS IS A GENERAL TEMPLATE THAT INCLUDES ALL HONEYWELL DEVICES CONNECTED TO
APPROPRIATE INPUT, OUTPUT TERMINALS ON LCBS CONNECT CONTROLLER.
.
C7250A
OA SENSOR
CTP-10-050-VDC-001
FAN, COMPRESSOR
CURRENT TRANSFORMER
(SELF POWERED)
LCBS CONNECT – COMPONENTS SHOWN
TR40-H-C02
CARBON
DIOXIDE
SENSOR
MCR36707
Содержание LCBS Connect