BCU 580 · Edition 11.15l
56
Parameters
Name
Parameter
Value range
Description
Factory default
settings
Air actuator can be activated externally on
49
0
1
Cannot be activated
Can be activated externally
0
Air actuator in the event of fault
50
0
1
Cannot be activated
Can be activated externally
1
51
0
1
2
3
4
Off
Tightness test before start-up
Tightness test after shut-down
Tightness test before start-up and after shut-down
Proof of closure function
0
52
2
3
4
V2
V3
V4
2
56
3
5 – 25
30 – 3600
Time in seconds
in 5 s steps
in 10 s steps
10
59
2 – 25
Time in seconds
2
61
0 – 250
Time in seconds
0
62
0 – 3600
Time in seconds
0
67
0
1
Unlimited
5 minutes
1
68
23
24
Purge with Low signal
Purge with High signal
24
69
0
8
13
Off
AND with emergency stop (trm. 46)
Max. capacity position feedback (IC 40/RBW)
0
70
0
8
Off
AND with emergency stop (trm. 46)
0
71
0
8
20
Off
AND with emergency stop (trm. 46)
LDS ignition position check
0
72
0
8
21
Off
AND with emergency stop (trm. 46)
Multi-flame control (MFC) start-up conditions
0
73
0
8
22
Off
AND with emergency stop (trm. 46)
Multi-flame control (MFC) operating conditions
0
▼