BCU 580 · Edition 11.15l
79
Parameters
Operating mode 11
Operating mode 11 allows cyclic operation (ON/OFF
and OFF/Low/High/OFF).
The actuator IC moves to the “High fire” position during
the controller enable procedure. There is no timeout ac-
tive in this case.
t [s]
t [s]
t1
t2
t3
t4
t5
t6
DI 1
DI 2
Purge
Closed
Ignition
High
fire
BCU
IC 40 (operating mode 11)
Signal at
terminal
Position
Butterfly valve position
55
53
OFF
OFF
Closed
Closed
ON
OFF
Ignition
Minimum/Ignition capacity
ON
ON
High-fire rate
High-fire rate
OFF
ON
Purge
Maximum capacity
Operating mode 27
During the controller enable procedure, the actuator
IC 40 can be adjusted infinitely between the positions
for maximum and minimum capacity using its ana-
logue input (terminals 18 and 19). There is no timeout
active in this case.
t [s]
t [s]
t1
t2
t3
t4
t5
t6
0–20
mA
DI 1
DI 2
Purge
Closed
Ignition
BCU
IC 40 (operating mode 27)
Signal at
terminal
Position
Butterfly valve position
55
53
OFF
OFF
Closed
Closed
ON
OFF
Ignition
Minimum/Ignition capacity
ON
ON
0 – 20 mA
Any position between minimum and
maximum capacity
OFF
ON
Purge
Maximum capacity
▼