Parameters
10 .3 .4 Safety time 1 t
SA1
Parameter 94
During the safety time 1 t
SA1
, the flame (pilot flame) is
ignited. It can be set to 2, 3, 5 or 10 s.
t
SA1
t
Z
04
06
07
08
02
03
00
t
t
FS1
t
SA2
t
FS2
5
13
V1
57
V4
1
14
V2
2
ϑ
1
ϑ
2
8
4
88
1
46
11
9
41
42
L1
1
43
2
17-18
Safety time 1 starts with the application of the
ϑ
1 sig-
nal (terminal 1). The valves open at the start of safety
time 1. The fuel supply to burner 1 is released so that
a flame can form. If no flame is detected at the end of
safety time 1, the valves are closed again. Depending
on parameter 07 (Burner 1 start-up attempts), the BCU
reacts either with an immediate safety shut-down with
fault lock-out (P07 = 1) or with one or two additional
start-up attempts (P07 = 2 or 3). The BCU will complete
a maximum of three start-up attempts.
Safety time 1 must be determined on the basis of cur-
rent national standards and regulations. The burner ap-
plication and the burner capacity are the main criteria
for this.
If the
ϑ
1 signal (terminal 1) drops out during safety
time 1, the valves will not be switched off until the end
of safety time 1.
10 .3 .5 Flame proving period 1 t
FS1
Parameter 95
Flame proving period 1 (t
FS1
) can be parameterized
to enable the flame on burner 1 to stabilize after the
elapse of safety time 1. Only when the flame proving
period has elapsed will the next program steps be initi-
ated by the BCU. The flame proving period can be set
between 0 and 20 s.