
BCU 580 · Edition 11.15l
120
BCM 500
15 .4 Installation
Installation position: vertically upright, horizontal or
tilted to the left or right.
The BCM mounting is designed for horizontally aligned
35 × 7.5 mm DIN rails.
G1
G2
G3
XXX ADR
G1
G2
G3
XXX AD
R
G1
G2
G3
XXX AD
R
If the DIN rail is aligned vertically, end clamps are re-
quired (e.g. Clipfix 35 by Phoenix Contact) to prevent
the control unit from slipping.
Install in a clean environment (e.g. a control cabinet)
with an enclosure ≥ IP 54, whereby no condensation is
permitted.
15 .5 Selection
Code
Description
BCM
Bus module
500
Series 500
S0
Standard communication
B2
Profinet
/3
Two RJ45 sockets
-3
Three-point step control via bus
Order No.: 74960663
15 .6 Technical data
Electrical data
Power consumption: 1.2 VA.
Power loss: 0.7 W.
Mechanical data
Dimensions (W × H × D):
32.5 × 115 × 100 mm.
Weight: 0.3 kg.
Environment
Ambient temperature:
-20 to +60°C (-4 to +140°F).
Storage temperature:
-20 to +60°C (-4 to +140°F).
Climate: no condensation permitted.
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 54 (for installation in a
control cabinet).