BCU 580 · Edition 11.15l
46
Profinet
“Remaining times of the valve proving system”
module (device
➔
controller) – slot 7
Only for BCU..C1.
The module in BCU..C0 contains no information.
This module transfers the remaining time of the valve
proving system from the BCU..C1 to the PLC. The re-
maining time occupies 2 bytes.
The valve check runs parallel to other time-related pro-
cesses, e.g. pre-purge. To display the remaining time
of the valve proving system separately, it is transferred
separately.
Bit Byte n
Byte n+1
Data type Format
Value
0
Remaining times of the
valve proving system
Word
DEC
0 – 6554
(0 – 6554 s)
1
2
3
4
5
6
7
“PLC output information” module (device
➔
controller) – slot 8
This module transfers information on signals which the
PLC uses to control the BCU back to the PLC. This al-
lows the signal transfer from the PLC to the BCU to be
checked.
Bit Byte n
Format
0
Reset
BOOL
1
Burner 1 start
BOOL
2
External air ON
BOOL
3
Pre-purge ON
BOOL
4
Free
BOOL
5
menox ON
BOOL
6
Open control element, three-point step Open
1)
BOOL
7
Close control element, three-point step Close
1)
BOOL
1)
Only with three-point step control via bus.
▼