BCU 580 · Edition 11.15l
78
Parameters
IC 40
Parameter 40 = 2: with IC 40.
To ensure that the actuator IC 40 can be operated on
the BCU..F1, P40 = 2 (capacity control) must be set.
The operating mode of actuator IC 40 may be param-
eterized to 11 or 27.
N
IC 40
PE
19 18
16 15 14
12 11 10
8 7
5 4
2 1
A
AC
D
DC
M
mA
L N
22 21 20
R..
53
54
55
56
52
1
2
3
46
45
65
66
67
68
49
50
51
17
18
37
38
13
14
15
BCU 580..F1
3,15AT
µC
88
c
c
41
42
24V
DC
5 6
9
11 12
10
7
62 61
The positions for maximum capacity and ignition
capacity can be set using the actuator. Terminal 51
checks whether the position for maximum capacity has
been reached. Terminal 52 checks the position for igni-
tion capacity. If the position is not reached within the
timeout time of 255 s, a safety shut-down of the BCU
will be performed. A fault message (
A
,
A
or
A
) will be
displayed, see page 51 (Fault signalling).
If a controller enable is active, the control system is
enabled for operation via the outputs at terminals 53
and 55.
▼