
BCU 580 · Edition 11.15l
96
Parameters
10 .7 .2 Relief valve (VPS)
Parameter 52
One of the valves connected to terminal 14, 15 or 57
can be selected to discharge the test volume during a
tightness test.
V2
V3
V4
PZ
µC
VAS
p
u
/2
14 15
13
45
52
55
54
53
56
57
38
37
18
17
V
p1
V2
V3
V4
14 15 57
Parameter 52 = 2: V2. The test volume is discharged via
the valve connected to terminal 14.
Parameter 52 = 3: V3. The test volume is discharged via
the valve connected to terminal 15.
Parameter 52 = 4: V4. The test volume is discharged via
the valve connected to terminal 57.
10 .7 .3 Measurement time V
p1
Parameter 56
The required measurement time must be determined
according to the requirements of the appropriate appli-
cation standards, e.g. EN 1643.
BCU 56x..C1
µC
P
13
14
45
p
u
/2
TC
PZ
>750°
ϑ
1
2
3
p
u
/2
PZ
V
p1
V1
V2
The required measurement time for the tightness test
of V
p1
can be set using parameter 56. The possible set-
tings are 3 s, 5 to 25 s (in 5 s steps) or 30 to 3600 s (in
10 s steps).
See also page 33 (Measurement time t