3.2 WIRING – STANDARD, CONTINUED
SPECIFICATIONS
WEIGHT : 6.6 lbs. (3.0 kg) WITH CAMERA
POWER REQUIREMENTS AT DOME: 24VAC, 50/60 Hz, 1.1A
NOTES:
1. TERMINAL STRIPS ACCEPT 18-22AWG WIRE
IF LARGER OR SMALLER WIRE IS REQUIRED, 18-22AWG MUST BE SPLICED
ONTO FIELD WIRE BEFORE INSERTING INTO TERMINAL STRIP.
2. ALL DIMENSIONS IN PARENTHESES ARE IN MILLIMETERS.
3. POWER SOURCE MUST BE 24VAC 10% AT POWER SUPPLY.
±
4. DATA CABLE SHIELD NOT CONNECTED AT DOME.
24Vac
Ground
24Vac
RX -
RX+
TX+
TX -
No Connection
TERMINAL STRIP TB1
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
Alarm 1
Common
Alarm 2
Common
Alarm 3
Common
Alarm 4
Common
TERMINAL STRIP TB2
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
ALIGNMENT TAB
CONTROL DATA
POWER
F1 1.6A 250V
LED POWER INDICATOR
REMOVABLE TOP PLATE
ALIGNMENT TAB
ALARM TERMINAL
STRIP
VIDEO BNC
CONNECTOR
J4
F1
Jumper W1
Jumper W2
Jumpers W3 & W4
Terminated Position 1 and 2 Last Dome on Data Loop
Unterminated Positions 2 and 3 All Intermediate Domes on Data Loop
Positions 2 and 3 All Domes
2-wire Positions 1 and 2 All Domes
AWG
22
20
18
16
14
12
MAX. DISTANCE TO DOME
65 FEET (19 METERS)
100 FEET (30 METERS)
160 FEET (48 METERS)
260 FEET (79 METERS)
420 FEET (128 METERS)
650 FEET (198 METERS)
24 VAC POWER @1.1A
Figure 12: Standard Wiring – Pendant Housing
Rev. 1.02
28
900.0696
1-Aug-06
Содержание HD6 Series
Страница 1: ...HD6 Series Housings Installation Manual 900 0696 August 2006 Rev 1 02 ...
Страница 4: ...Rev 1 02 iv 900 0696 1 Aug 06 ...
Страница 8: ...Rev 1 02 viii 900 0696 1 Aug 06 Notes ...
Страница 12: ...Rev 1 02 2 900 0696 1 Aug 06 Notes ...
Страница 28: ...Rev 1 02 18 900 0696 1 Aug 06 Notes ...
Страница 51: ...Rev 1 02 41 900 0696 1 Aug 06 Notes ...
Страница 52: ...Rev 1 02 42 900 0696 1 Aug 06 Notes ...
Страница 53: ...Rev 1 02 43 900 0696 1 Aug 06 Notes ...
Страница 54: ...Rev 1 02 44 900 0696 1 Aug 06 Notes ...
Страница 55: ...Rev 1 02 45 900 0696 1 Aug 06 Notes ...