– 15 –
Register through the AlarmNet Direct Website
To register the module via the website (if you are already signed up for this service), go to:
https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
Log in and follow the on-screen prompts.
If you are not signed up for this service, click on “Dealer Signup” from the login screen to gain access to
the Honeywell web-based programming.
You will be instructed how to proceed upon completing the sign-up form. Only one sign-up per dealer is
required. Once an initial user is established, additional logins may be created by that user.
NOTE:
Central Stations sign up by contacting AlarmNet Administration at 800-222-6525 option 3.
Please have the following information available when programming the device:
1.
Primary City ID (two-digit number)
2.
Primary Central Station ID (two-digit hexadecimal number)
3.
Primary Subscriber ID (four-digit number)
4.
MAC ID and MAC CRC number (located on outside of box and on label inside module) or MIN
number of the device you are replacing.
Once module is registered, you may log out of the AlarmNet Direct website.
Register Using the Test Message/Registration Switch
Initiate the registration sequence by clicking the Test Message/Registration Switch three times. You
can monitor the registration process by viewing the Status Display. The Message (yellow) LED and the
Status (green) LED will blink slowly in unison while registration is in progress. Once the registration
has been completed successfully, the GSMVLP4G/GSMVLPCN4G enters normal operating mode; the
Status (green) LED goes out and the Message (yellow) LED is lit to indicate that the power-on / reset
message is waiting to be sent. This message will appear at the receiving station as “E339 803”. The
description may read “Trouble – Exp. Mod. Reset”. If registration is not validated within 90 seconds,
the GSMVLP4G/GSMVLPCN4G times out, and the (green) LED will be lit (solid).
Register Using the Programming Tool
The interactive registration feature allows the installer to register the GSMVLP4G through a series of
keyboard commands on the 7720P Programming Tool. This method of registration lets the installer
monitor the registration process.
Registering …
Once the installation is complete, press the
[
↑
]
key on the 7720P. The
registration message is sent and the unit waits for the acknowledgment.
Registration
SUCCESS
If this is a new installation and the city, central station, and customer numbers
have been correctly entered, the GSMVLP4G is registered and this message is
displayed. The GSMVLP4G is now in full service and available for alarm
reporting to the central station.
Possible Errors
Registration BAD
Timed Out
Displayed if no response to the registration request is received.
Registration BAD
Pri Sub ID BAD
Indicates the city, central station, or customer number for the labeled
account(s) is not accepted. The ID information was either entered in error, or
the central station failed to pre-authorize programmed ID numbers with
AlarmNet customer service.