S-Quad & S3 Mk2/Mk3
Sector
setup
For any Sounder to make a sound,
Audible On
must be ticked against that
Signal.
If Speech is to be used, Speech
Operation must be ticked against that
Signal.
VAD/Str Actioned if ticked will flash any
VADs or Strobes for that Signal.
Note: A Combined Sounder/VAD must
have at least one output working.
For Standard Panel Signals (No Voice Messages) set
Low/Attn Tone
AND
High/Message
to
00.
Also Ensure that
Speech Operation
is unticked.
To use Voice Messages (Voice Enabled Devices) set
Low/Attn Tone
to
00
and set the
High/Message
to the required Message. Ensure that
Speech
Operation
is ticked.
Codes:
00
= standard tone for signal
01
= message 1 (bell ring)
02
to
05
= voice message 2 to 5
Note: If no Sounder/Voice Devices are in this Sector the Low/Attn Tone
and High Message will have the value of FF
Strobe period:
(2 seconds
between Flashes)
Pre speech & post speech:
Gap between attention tone
and message
*
*
*
*
Sndr - Sector can be setup
E.g. Sector 1 Loop 2;
on receipt of a sig 2 instruction, all ‘sounders’ will provide standard ‘evac’ attention tone
followed by message 5 in a loop and VAD/Strobes will flash with a 2 sec on/off rate
Warning
– Do not use Voice Messages if you have a mix of Voice and
Non-Voice enabled devices in the same sector.
Содержание Gent Compact Plus
Страница 1: ...Vigilon Plus Basic Commissioning Training ...
Страница 4: ...Vigilon Plus 4 6 Loop Panels ...
Страница 16: ...Compact Plus 2 loops ...
Страница 18: ...Main Control Board 0 Loop Card 1 Loop Card 2 Network Card 10 NVM Card 14 Compact Plus Cards Micro SD card ...
Страница 21: ...Your Turn Power Up ...
Страница 24: ...INFO STATUS CARD Card Status Type in a card number in the range of 0 15 ENTER ...
Страница 26: ...Vigilon System Loop Architecture ...
Страница 27: ...Main Loop PRESS HARD TO PRESS HARD TO Vigilon System Loop Architecture L1 End 1 L2 End 2 ...
Страница 30: ...Soft Addressing ...
Страница 36: ...SAFE Addressing ...
Страница 44: ...Analogue Detection ...
Страница 49: ...Digital Outputs and Analogue Channels On Off low tone Hi tone ...
Страница 61: ...Site Information ...
Страница 63: ...Labelling ...
Страница 67: ...Zones ...
Страница 74: ...Condition Code Analysis Subfault Exception BS panel V3 EN54 panel V4 ...
Страница 76: ......
Страница 84: ...S Quad Remote LED Output can be configured to control a remote LED 13449 01 Monitored or un monitored wiring ...
Страница 93: ... Other Panel Functions ...
Страница 105: ...VigInSite ...
Страница 112: ...Loop Diagnostic Tool LDT ...
Страница 117: ...LDT Panel Overview Panel Overview Panel cards and versions Loop overview Click the required View Loop Button ...
Страница 119: ...LDT Earth Fault Earth fault Detected Click to Locate Earth fault The Loop will now reallocate ...
Страница 120: ...LDT Earth Fault ...
Страница 122: ...LDT Reports cont Extracts from an Engineer report ...
Страница 123: ...EN54 Part 23 Overview ...
Страница 126: ...Wall Mounted VADs CEILING MOUNTED C 6 16 16m ...