SAFE Addressing
SAFE (
S
oftware
A
llocated
F
irmware
E
ncoded) addressing - Is a method of loop device addressing whereby
the EEPROM of a device stores the address. This address is not lost even if the device is removed physically.
A device has to be initially allocated an address by the loop card and then can be SAFE addressed ONLY
via the Panel’s Setup Menu.
A device can be SAFE addressed with the address it has been allocated
or
any other address that currently
doesn’t exit on the loop in the range 1 to 207.
A single device or range of devices can be SAFE addressed or unSAFE’d via the panel’s setup Menu
Type the Current
Device address OR
range of Device
Addresses
SET UP
SET UP
DEVICE
LOOP
Type the Loop
Number
SAFE
**Type the Desired
Device address OR
Desired range of
Device Addresses
ENTER
Card x Successful
** TYPE 0 to remove the device(s)’ SAFE Address
Содержание Gent Compact Plus
Страница 1: ...Vigilon Plus Basic Commissioning Training ...
Страница 4: ...Vigilon Plus 4 6 Loop Panels ...
Страница 16: ...Compact Plus 2 loops ...
Страница 18: ...Main Control Board 0 Loop Card 1 Loop Card 2 Network Card 10 NVM Card 14 Compact Plus Cards Micro SD card ...
Страница 21: ...Your Turn Power Up ...
Страница 24: ...INFO STATUS CARD Card Status Type in a card number in the range of 0 15 ENTER ...
Страница 26: ...Vigilon System Loop Architecture ...
Страница 27: ...Main Loop PRESS HARD TO PRESS HARD TO Vigilon System Loop Architecture L1 End 1 L2 End 2 ...
Страница 30: ...Soft Addressing ...
Страница 36: ...SAFE Addressing ...
Страница 44: ...Analogue Detection ...
Страница 49: ...Digital Outputs and Analogue Channels On Off low tone Hi tone ...
Страница 61: ...Site Information ...
Страница 63: ...Labelling ...
Страница 67: ...Zones ...
Страница 74: ...Condition Code Analysis Subfault Exception BS panel V3 EN54 panel V4 ...
Страница 76: ......
Страница 84: ...S Quad Remote LED Output can be configured to control a remote LED 13449 01 Monitored or un monitored wiring ...
Страница 93: ... Other Panel Functions ...
Страница 105: ...VigInSite ...
Страница 112: ...Loop Diagnostic Tool LDT ...
Страница 117: ...LDT Panel Overview Panel Overview Panel cards and versions Loop overview Click the required View Loop Button ...
Страница 119: ...LDT Earth Fault Earth fault Detected Click to Locate Earth fault The Loop will now reallocate ...
Страница 120: ...LDT Earth Fault ...
Страница 122: ...LDT Reports cont Extracts from an Engineer report ...
Страница 123: ...EN54 Part 23 Overview ...
Страница 126: ...Wall Mounted VADs CEILING MOUNTED C 6 16 16m ...