Node 1 Domain 1
Port 0: 1200 Off
Port 1: 38400 None
Port 2: 38400 None
Port 3: 38400 None
Connecting the Commissioning Tool to the Panel
Before we can use the Commissioning Tool to communicate
with the Fire Panel we need some details about the panel.
INFO > STATUS > CARD {0} > ENTER
Card 0:
Fault 0 Disable 0 Warning 0
Controller (2) Version 4.37 21/11/06
Node Address
On power up, a new EN Panel
(Without a Network card
Fitted) the node address will
not be set up.
To Change or Setup the Node
Address:
TestEng > Usercode >Config
> Comms > Address
{type in required node
address in the range of 1 to
32} > Enter
Domain Number
On an EN Panel by default
this will be set at
Domain 1.
To Change the Domain
Number if required:
TestEng > Usercode >
Config > Comms > Domain
{type in required Domain
address in the range of 1 to
255} > Enter
Version
3.xx = BS
4.xx = EN
RS232 Ports
Compact Only
Communication Port and Baud Rate:-
Ports 1 & 2 (Compact Panel only) are the serial (RS232) Ports and
Port 3 is the USB port. To change the baud rate use:-
TestEng > Usercode > Config > Comms > Card {0} Enter > {Type the Port No} > Enter > Baud > Enter
> {Use the Previous and Next options to adjust the Baud rate} > Enter
Содержание Gent Compact Plus
Страница 1: ...Vigilon Plus Basic Commissioning Training ...
Страница 4: ...Vigilon Plus 4 6 Loop Panels ...
Страница 16: ...Compact Plus 2 loops ...
Страница 18: ...Main Control Board 0 Loop Card 1 Loop Card 2 Network Card 10 NVM Card 14 Compact Plus Cards Micro SD card ...
Страница 21: ...Your Turn Power Up ...
Страница 24: ...INFO STATUS CARD Card Status Type in a card number in the range of 0 15 ENTER ...
Страница 26: ...Vigilon System Loop Architecture ...
Страница 27: ...Main Loop PRESS HARD TO PRESS HARD TO Vigilon System Loop Architecture L1 End 1 L2 End 2 ...
Страница 30: ...Soft Addressing ...
Страница 36: ...SAFE Addressing ...
Страница 44: ...Analogue Detection ...
Страница 49: ...Digital Outputs and Analogue Channels On Off low tone Hi tone ...
Страница 61: ...Site Information ...
Страница 63: ...Labelling ...
Страница 67: ...Zones ...
Страница 74: ...Condition Code Analysis Subfault Exception BS panel V3 EN54 panel V4 ...
Страница 76: ......
Страница 84: ...S Quad Remote LED Output can be configured to control a remote LED 13449 01 Monitored or un monitored wiring ...
Страница 93: ... Other Panel Functions ...
Страница 105: ...VigInSite ...
Страница 112: ...Loop Diagnostic Tool LDT ...
Страница 117: ...LDT Panel Overview Panel Overview Panel cards and versions Loop overview Click the required View Loop Button ...
Страница 119: ...LDT Earth Fault Earth fault Detected Click to Locate Earth fault The Loop will now reallocate ...
Страница 120: ...LDT Earth Fault ...
Страница 122: ...LDT Reports cont Extracts from an Engineer report ...
Страница 123: ...EN54 Part 23 Overview ...
Страница 126: ...Wall Mounted VADs CEILING MOUNTED C 6 16 16m ...