3.10 Loop 1 Control Parameters Set Up Group
Table 3-9 Control Group Function Prompts
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
PV SOURC
Process Variable Source
INP 1
IN AL1
INP 2
INP 1
PID SETS
Tuning Parameter Sets
1 ONLY
2KEYBD
2PV SW
2SP SW
1 ONLY
SW VALUE
Automatic Switchover
Value
Value in engineering units within
PV or SP range limits
0.00
LSP’S
Local Setpoint Source
1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
1 ONLY
RSP SRC
Remote Setpoint Source
NONE
IN AL1
INP 2
NONE
AUTOBIAS
Automatic Bias
ENABLE
DISABL
DISABL
SP TRACK
Local Setpoint Tracking
NONE
PV
RSP
NONE
PWR MODE
Power Up Mode Recall
MANUAL
A LSP
A RSP
AM SP
AM LSP
MANUAL
PWR OUT
TPSC Output Start-up
Mode
LAST
F’SAFE
LAST
SP HiLIM
Setpoint High Limit
0 to 100% of span input in
engineering units
1000
SP LoLIM
Setpoint Low Limit
0 to 100% of span input in
engineering units
0
ACTION
Control Output Direction
DIRECT
REVRSE
REVRSE
OUT RATE
Output Change Rate
ENABLE
DISABL
Does not apply to 3 Position Step
Control algorithm.
DISABL
PCT/M UP
Output Rate Up Value
0 to 9999% per minute
0
Содержание DC3300
Страница 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Страница 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 83: ......