Operation
5/00
UDC3300 Basic Model: DC330B User Manual
49
DIG IN1 or
DIG IN2
Selections
Display Indication
Action on Contact Closure
Returns (toggles) to original state when contact
opens, unless otherwise noted.
TIMER
Timer clock (
)
and time appear in
lower display.
Starts timer (momentary). Reopening switch has no
effect.
AM STA
Causes switch to Auto Manual Station mode.
ToTUNE
TUNE ON in lower
display
Starts the Accutune process.
SPinit
Forces the SP to initialize at the current PV value.
TRACK1
O blinks
Allows Output 1 to track Input 2.
TO RSP
RSP annunciator
blinks
Selects remote setpoint, if enabled.
RST FB
Allows Input 2 to override the internal reset value,
providing external reset feedback.
ToPURG
MAN blinks and
output value shows
in lower display
Forces loop to manual mode with the output values set to
the Output High Limit configuration.
LoFIRE
MAN blinks and
output value shows
in lower display
Forces loop to manual mode with the output set to the
Output Low Limit configuration.
MAN LT
Forces loop to manual mode, latched. Opening DI has no
effect on Mode. UDC remains in manual mode.
Keyboard Operation
Front panel keys have no effect on the digital input action in the closed state.
Digital Inputs 1 and 2 Combination Selections
Table 4-12 Digital Input Combinations “DIG IN1” or “DIG IN2”
Selections used in
Combination with
“DIG IN1” or “DIG
IN2”
Display Indication
Action on contact closure
Returns (toggles) to original state
when contact opens.
+PID2
PIDSET 2 in lower display
Selects PID set 2.
+ToDIR
Puts the controller into direct action.
+ToSP2
RSP blinks
Selects the second local setpoint.
+ToSP1
Selects the local setpoint.
+RUN
R indicator blinks
Starts or restarts RUN of SP RMP/PROG.
Содержание DC3300
Страница 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Страница 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 83: ......