4.3 Start-up Procedure
Table 4-3 Procedure for Starting Up the Controller
Step
Operation
Press
Action
1
Select
manual mode
MANUAL
AUTO
until “MAN” indicator is ON.
The controller is in manual mode.
2
Adjust the
output
▲
or
▼
to adjust the output value and ensure that the final control
element is functioning correctly.
Upper Display: PV value
Lower Display: OUT and the output value in %
3
Enter the
local setpoint
LOWER
DISPLAY
Upper Display: PV Value
Lower Display: SP and the local setpoint value
▲
or
▼
to adjust the local setpoint to the value at which you want
the process variable maintained.
The local setpoint cannot be changed if the Setpoint
Ramp function is running. “R” appears in the upper
display.
4
Select
automatic
mode
MANUAL
AUTO
until “A” indicator is ON.
The controller is in Automatic mode.
The controller will automatically adjust the output to
maintain the process variable at setpoint, if the controller
is properly tuned.
5
Tune the
controller
SET UP
Tuning will be required on the first startup. First enable
“TUNE” selection in the Accutune Group.
Refer to Tuning Set Up group to ensure that the proper
selections for PROP BD or GAIN, RATE MIN, and RSET
MIN, or RSET RPM have been entered.
Use Accutune to tune the controller as follows:
1. Adjust setpoint to the desired value.
2. Switch to Automatic mode by pressing the
MANUAL/AUTO key.
3. Initiate Tuning by:
•
Pressing the up arrow key when the lower display
prompt shows TUNE-OFF, or
•
Pressing the LOWER DISPLAY and Up arrow
keys simultaneously, or…
•
Using the Digital Input, if configured.
If it is necessary to stop or abort the tuning process, press
the MANUAL/AUTO key and the controller will return to
manual mode.
Содержание DC3300
Страница 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Страница 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 83: ......