Operation
52
UDC3300 Basic Model: DC330B User Manual
5/00
Using TUNE at Start-Up for Duplex (Heat/Cool)
Table 4-14 Procedure for Using TUNE at Start-up for Duplex
Step
Action
1
Heat Zone:
• Adjust Local Setpoint 1 to a value within the Heat zone.
• Put the controller in Automatic mode.
• Press the Lower Display and
▲
keys simultaneously to initiate Heat tuning.
The output will cycle between 50% and 100% (or high output limit). A large T
appears in the upper display until tuning is completed and final Heat parameters
are entered for PID set 1 in the Tuning group.
2
Cool Zone:
• Adjust Local Setpoint 2 to a value within the Cool zone.
• Put the controller in Automatic mode.
• Press the Lower Display and
▲
keys simultaneously to initiate Cool tuning.
The output will cycle between 0 % and 50 % (or low output limit). A large T
appears in the upper display until tuning is completed and final Cool parameters
are entered for PID set 2 in the Tuning group.
4.13 Entering a Security Code
The level of keyboard lockout may be changed in the Set Up mode. However,
knowledge of a security code number (0 to 4095) may be required to change from
one level of lockout to another. When a controller leaves the factory, it has a
security code of 0, which permits changing from one lockout level to another without
entering any other code number.
If you require the use of a security code, select a number from 0001 to 4095 and
enter it when the lockout level is configured as NONE. Thereafter, that selected
number must be used to change the lockout level from something other than NONE.
CAUTION
Write the number on the Configuration Record Sheet in Appendix C so
you will have a permanent record.
Table 4-15 Procedure to Enter a Security Code
Step
Operation
Press
Result
1
Enter Set Up
Mode
SET UP
Upper Display = SET UP
Lower Display = TUNING
2
Select any Set
Up Group
FUNCTION
LOOP 1/2
Upper Display = 0
Lower Display = SECUR
3
Security Code
Entry
▲
or
▼
To enter a four digit number in the upper display (0001 to
4095)
This will be your security code.
Содержание DC3300
Страница 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Страница 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 83: ......