Operation
5/00
UDC3300 Basic Model: DC330B User Manual
45
Set Tuning Constant Values for Each Set
There are specific tuning constants that must be set for each set. The procedure
below shows you how to access these constants and change their value.
Table 4-7 Procedure for Setting Tuning Constant Values
Step
Operation
Press
Action
1
Select
Tuning Set
Up Group
SET UP
until you see TUNING in the Lower Display
FUNCTION
LOOP 1/2
to successively display the available constants in the
Lower Display. The value is displayed in the Upper
Display.
2
Select the
tuning
constants
▲
or
▼
To change the value of any of the above listed prompts
in the lower display.
Switch Between Two Sets via the Keyboard (Without Automatic Switchover)
This procedure is operational only if 2 PID SETS was configured at the Control Set
Up group.
Table 4-8 Procedure for Switching PID SETS from the Keyboard
Step
Operation
Press
Action
1
LOWER
DISPLAY
until you see the PV value displayed in the Upper
Display and the PIDSETx in the Lower Display.
Access the
PID set
display
▲
or
▼
to change PIDSET1 to PIDSET2 or vice versa.
You can use Accutune on each set.
Содержание DC3300
Страница 1: ...Sensing and Control UDC3300 Basic Model DC330B User Manual 51 52 25 78 5 00 ...
Страница 26: ...Installation 18 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 70: ...Setpoint Rate Ramp Soak Program Operation 62 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 72: ...Environmental and Operating Conditions 64 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 74: ...Model Selection Guide 66 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 80: ...Position Proportional Calibration 72 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 82: ...Input Ranges 74 UDC3300 Basic Model DC330B User Manual 5 00 ...
Страница 83: ......