CIPer
TM
MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
31
31-00233-02
Wiring Terminals
The CIPer Model 50 is equipped with push-in terminal plugs.
Figure 23: Inserting/removing wires from push-in terminals
NOTE
•
With solid conductors, ferrules are prohibited.
•
Use only one conductor per push-in terminal.
•
If, nevertheless, two stranded wires are to be connected to a single push-in terminal, twin wire
end ferrules must be used.
Table 7. CIPer Model 50 push-in terminal wiring specifications
Plug gauge
0.0003… 0.002”
(
0.2 … 1.50 mm
)
Solid conductor H05(07) V-K
0.0003… 0.002”
(
0.2 … 1.50 mm
)
Stranded conductor H05(07) V-K
0.0003… 0.002”
(
0.2 … 1.50 mm
)
Stranded conductor with wire end ferrules (w/o
plastic collar)
0.0003… 0.002”
(
0.2 … 1.50 mm
)
Stripping length
0.4” +
0.04”
(10.0 +1.0 mm)
Terminal Assignment
Table 8. Terminal assignment
Terminal
no.
Signal
Description
WEB-
EHSERIESNX26XX
1
24V-0
Supply voltage (GND), int. connected with term. 31 and system
GND (term. 19+37)
X
2
24V~
supply voltage (24V)
X
3,4
-
Not used
-
5
BO1
Binary output 1. N.O. relay contact switching input power
connected to terminal 8
X
6
BO2
Binary output 2. N.O. relay contact switching input power
connected to terminal 8
X
7
BO3
Binary output 3. N.O. relay contact switching input power
connected to terminal 8
X
8
IN1,2,3
Common relay contact for BO1, BO2, and BO3
X
9
INX
Relay contact for BO4
X
10
BO4
Binary output 4. N.O. relay contact switching input power
connected to terminal 9
X
11
BO5
Binary output 5. N.O. relay contact switching input power
connected to terminal 12
X
12
IN5
Relay contact for BO5
X
13
IN6
Relay contact for BO6
X
14
BO6
Binary output 6. N.O. relay contact switching input power
connected to terminal 13
X