Troubleshooting
CIPer Model 50 Controller Troubleshooting
The following LEDs of the CIPer Model 50 controller can be used for troubleshooting purposes:
•
Power LED (green)
•
Status LED (red)
•
L1 and L2 LEDs (yellow)
•
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of CIPer Model 50
Table 28. CIPer Model 50 controller power LED
Case
Power LED
Meaning
Remedy
1
ON
Normal operation.
No action necessary.
2
OFF
Power supply not OK.
•
Check power supply voltage.
•
Check wiring.
•
If problem persists, replace hardware.
Status LED (red) of CIPer Model 50
Table 29. CIPer Model 50 controller status LED
Case
Status LED
Meaning
Remedy
1
OFF after power-up
Normal operation.
No action necessary.
2
ON continuously after
power-up
Indicates an active alarm;
is controlled by WEBs-
Alarm System; is
configurable.
•
Try powering down and then powering
up the CIPer Model 50 controller.
•
If problem persists, replace hardware.