CIPer
TM
MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
81
31-00233-02
BALCO 500 Temperature Characteristics
Same voltages for inputs of Panel Bus I/O Modules and Onboard inputs.
BALCO 500 Temperature
BALCO 500 Temperature
Temp[°F]
Temp [°C]
Resistance (
Ω
)
Temp[°F]
Temp[°C]
Resistance (
Ω
)
-40.0
-40.0
379.35
91.4
33
520.21
-38.2
-39.0
381.10
93.2
34
522.33
-36.4
-38.0
382.85
95.0
35
524.45
-34.6
-37.0
384.61
96.8
36
526.58
-32.8
-36.0
386.37
98.6
37
528.71
-31.0
-35.0
388.14
100.4
38
530.85
-29.2
-34.0
389.91
102.2
39
532.99
-27.4
-33.0
391.69
104.0
40
535.14
-25.6
-32.0
393.47
177.8
81
627.58
-23.8
-31.0
395.26
179.6
82
629.95
-22.0
-30.0
397.05
181.4
83
632.31
-20.2
-29.0
398.85
183.2
84
634.68
-18.4
-28.0
400.65
185.0
85
637.06
-16.6
-27.0
402.46
186.8
86
639.44
-14.8
-26.0
404.27
188.6
87
641.83
-13.0
-25.0
406.09
190.4
88
644.22
-11.2
-24.0
407.91
192.2
89
646.62
-9.4
-23.0
409.74
194.0
90
649.02
-7.6
-22.0
411.57
195.8
91
651.43
-5.8
-21.0
413.41
197.6
92
653.84
-4.0
-20.0
415.25
199.4
93
656.26
-2.2
-19.0
417.10
201.2
94
658.68
-0.4
-18.0
418.95
203.0
95
661.11
1.4
-17.0
420.81
204.8
96
663.54
3.2
-16.0
422.68
206.6
97
665.98
5.0
-15.0
424.54
208.4
98
668.42
6.8
-14.0
426.42
210.2
99
670.87
8.6
-13.0
428.30
212.0
100
673.32
10.4
-12.0
430.18
213.8
101
675.78
12.2
-11.0
432.07
215.6
102
678.24
14.0
-10.0
433.96
217.4
103
680.71
15.8
-9.0
435.96
219.2
104
683.18
17.6
-8.0
437.77
221.0
105
685.66
19.4
-7.0
439.68
222.8
106
688.14
21.2
-6.0
441.59
224.6
107
690.63
23.0
-5.0
443.51
226.4
108
693.12
24.8
-4.0
445.43
228.2
109
695.62
26.6
-3.0
447.36
230.0
110
698.13
28.4
-2.0
449.30
231.8
111
700.64
30.2
-1.0
451.24
233.6
112
703.25
32.0
0.0
453.18
235.4
113
705.67
33.8
1
455.13
237.2
114
708.19
35.6
2
457.09
239.0
115
710.72
37.4
3
459.05
240.8
116
713.25