CIPer
TM
MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
7
31-00233-02
WEEE DIRECTIVE
WEEE: Waste Electrical and Electronic Equipment Directive
•
At the end of the product life, dispose of the packaging and product in an appropriate
recycling center.
•
Do not dispose of the device with the usual domestic refuse.
•
Do not burn the device.
Standards and Approvals
Degree of Protection:
IP20 (mounted on walls, with two accessory MVC-80-AC1 covers)
IP30 (mounted in cabinet doors, with accessory MVC-80-AC2)
Device meets EN 60730-1, EN 60730-2-9, UL60730, and UL916.
Refer to Code of Practice standards IEC 61000-5-1 and -2 for guidance.
The device complies with Ethernet Protocol versions IEEEC 802.3.
The device supports BACnet IP and BACnet MS/TP communications as per ANSI / ASHRAE 135-2012
Specifications of Controller
Table 2. CIPer Model 50 specifications
Power supply
19 … 29
VAC, 50/60 Hz or
20 … 30
VDC
Power consumption
DC: 7 W (max 9 W)
AC: 10 VA (max 12 VA)
Heat dissipation
Max. 9 W at DC power supply
Max. 9 W at AC power supply
Current consumption
DC: 300 mA (max. 375 mA)
AC: 400 mA (max. 500 mA)
Ambient temperature
32 … 104 °F
(0
…
40 °C) (wall-mounting)
32 … 122 °F
(0
…5
0 °C) (cabinet/door mounting)
Storage temperature
-
4 …
+158 °F (-20
…+
70 °C)
Humidity
5 … 95% rh.
non-condensing
Dimensions
Degree of protection
IP20 (mounted on walls, with two accessory MVC-80-AC1 covers)
IP30 (mounted in cabinet doors, with accessory MVC-80-AC2)
Fire class
V0
Weight
1.33 lb (0.6kg) excl. packaging