EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
3
EN1Z-1005GE51
R0216
SPECIFICATIONS OF CONTROLLER
Table 2. EAGLEHAWK specifications
Power supply
19 … 29 VAC, 50/60 Hz or
20 … 30 VDC
Power consumption
typically dc: 5 W; max. 6 W
typically ac: 9 VA; max. 11 VA
Current consumption
typically dc: 210 mA; max. 240 mA
typically ac: 370 mA; max. 410 mA
Ambient temperature
0 … 40 °C (wall-mounting)
0 … 50 °C (cabinet/door mounting)
Storage temperature
-20 … +70 °C
Humidity
5 … 95% r.h. non-condensing
Dimensions
See Fig. 17 and Fig. 18.
Degree of protection
IP20 (mounted on walls, with two accessory MVC-80-AC1 covers)
IP30 (mounted in cabinet doors, with accessory MVC-80-AC2)
Fire class
V0
Weight
0.6 kg (excl. packaging)
SYSTEM OVERVIEW
Overview of Hardware
Table 3. Overview of hardware
feature
description
max. cable length
no.
bus interfaces
RS485-1, isolated; for BACnet MS/TP, Panel Bus
(1)
, Modbus RTU Master comm., etc.
(1)
1200 m
1
RS485-2, non-isolated; for BACnet MS/TP, Panel Bus
(1)
, Modbus RTU Master comm., etc.
(1)
1200 m
1
Ethernet / RJ45 socket (for e-mailing, browser access, BACnet IP comm., etc.)
100 m
1
USB 2.0 Device Interface (as Network Interface)
3 m
1
USB 2.0 Host Interface (max. 500 mA)
3 m
1
RS232 M-Bus communication via PW3 / PW20 / PW60 converters
(2)
1000 m
1
LEDs
power LED (green)
-- 1
status LED (red, controllable by firmware)
-- 1
LED L1 (yellow)
-- 1
LED L2 (yellow)
-- 1
bus status LEDs (for isolated RS485-1 interface)
-- 2
Socket for
CLEAHMI21
RJ45 socket for connection of CLEAHMI21 External HMI (supported in future releases)
5 m
1
(1)
Depending upon baud rate. For max. cable lengths, see section "RS485 Standard" on pg. 8. In the case of the Panel Bus, see also section
"Panel Bus Considerations" on pg. 15. In the case of the BACnet MS/TP Bus, see also section "BACnet MS/TP Bus Considerations" on pg. 20.
In the case of the Modbus, see also section "Modbus Considerations" on pg. 23.
(2)
Depending upon baud rate. See also section "M-Bus Considerations" on pg. 25.
NOTE:
The communication protocols listed here are only examples. The RS485-1 and RS485-2 interfaces also support
Modbus RTU Slave communication, as well as any RS485-based driver available within the Niagara Ecosystem.